Function; Cool Mode Operation - Technibel MCAF92R5TA Technical Data & Service Manual

Split system air conditioner indoor unit
Table of Contents

Advertisement

5.FUNCTION

5-1 Cool Mode Operation

(RT - SPT) [
+3
+2
+1
0
-1
ON
COMP
OFF
ON
OFAN
OFF
H
M
IFAN
L
ON
RV
OFF
In Cool Mode, the operation of the Compressor (COMP), Outdoor Fan (OFAN) and Indoor Fan (IFAN)
are determined by the difference between the Room Temperature (RT) and the Set Point Temperature
(SPT) as in the graph above.
Notes:
1. In this graph, the IFAN is operating in the "Auto Fan Speed" setting. If the user has selected the low,
medium or high fan speed, the IFAN will run constantly at that speed only.
2. In addition to the value of (RT-SPT), the operations of the relays are also controlled by protection
delays. For example, (a) the minimum On/Off time of the COMP is 5 min and 3 min respectively, and
(b) the IFAN can change speed only after it has operated at the same speed for 30 sec.
o
c]
over 3 min
over 30 sec
over 5 min
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcaf72r5taMcaf122r5taKaf94r5ta series

Table of Contents