Trane CVHH CenTraVac Installation, Operation And Maintenance Manual page 25

Water-cooled chillers with tracer adaptiview control
Table of Contents

Advertisement

Figure 10. Isolation spring placement
Isolator Configuration 1
2
Condenser
Evaporator
1
Length
Isolator Configuration 2
2
Condenser
5
Evaporator
1
Length
Table 8. Isolation spring placement
Width
EVSZ
CDSZ
in.
200L
200L
112.2
220L
220L
119.4
200L
20HL
132.3
220L
22HL
142.5
160M
20HM
127.3
200L
220L
112.3
160M
200M
106.4
100M
100M
104.1
100L
100L
104.1
130M
130M
109.3
100M
10HM
118.2
130M
13HM
123.4
Spring isolators typically ship assembled and ready for
installation. To install and adjust the isolators properly,
follow the provided instructions.
N N o o t t e e : : Do NOT adjust the isolators until the chiller is
piped and charged with refrigerant and water.
I I m m p p o o r r t t a a n n t t : : Do NOT block any serviceable components
such as the lubrication system with field-
installed devices such as spring isolators.
1. Position the spring isolators under the chiller as
shown in the preceding figure. Ensure that each
isolator is centered in relation to the tube sheet.
CVHH-SVX001G-EN
4
Width
3
Origin:
Right front corner of
evap right front foot
4
Width
6
Evap
Width
3
Evap Width
cm
in.
cm
285.0
67
170.2
303.3
74
188.0
336.0
67
170.2
361.0
74
188.0
323.3
61
154.9
285.2
67
170.2
270.3
61
154.9
264.4
264.4
277.6
300.2
313.4
Length
Isolator
Config
in.
cm
180
457.2
2
180
457.2
2
180
457.2
2
180
457.2
2
160
406.4
2
180
457.2
2
160
406.4
2
160
406.4
1
180
457.2
1
160
406.4
1
160
406.4
1
160
406.4
1
N N o o t t e e : : Spring isolators shipped with the chiller may
not be identical. Compare the data provided
in the unit submittal package to determine
proper isolator placement.
2. Set the isolators on the sub-base; shim as
necessary to provide a flat, level surface at the
same elevation for the end supports.
I I m m p p o o r r t t a a n n t t : : Support the full underside of the
isolator base plate; do NOT straddle
gaps or small shims.
3. If required, screw the isolators to the floor through
the slots provided, or cement the pads.
N N o o t t e e : : Fastening the isolators to the floor is not
necessary unless specified.
I I n n s s t t a a l l l l a a t t i i o o n n : : M M e e c c h h a a n n i i c c a a l l
Origin to Center
Origin to Center
of Rear Pad
of Middle Pad
in.
cm
in.
105.7
268.5
60.5
112.9
286.8
67.5
125.8
319.5
60.5
136.0
345.4
67.5
120.8
306.8
54.5
105.8
268.7
60.5
99.9
253.7
54.5
97.6
247.9
97.6
247.9
102.8
261.1
111.7
283.7
116.9
296.9
cm
153.7
171.5
153.7
171.5
138.4
153.7
138.4
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Centravac cvhh

Table of Contents