S S t t a a r r t t - - u u p p a a n n d d S S h h u u t t - - d d o o w w n n
the past seven days that occurred while the chiller
was operating. You can use it to help determine if a
leak is present on the high side or the low side of
the chiller.
P P u u m m p p o o u u t t C C h h i i l l l l e e r r O O f f f f — — 7 7 D D a a y y s s . . Indicates the
percentage of the total purge pump-out time during
the past seven days that occurred when the chiller
was not operating. You can use it to help determine
if a leak is present on the high side or the low side
of the chiller.
P P u u m m p p o o u u t t — — L L i i f f e e . . Indicates the total purge pump-out
time that has accumulated over the life of the
purge.
P P u u r r g g e e R R f f g g t t C C p p r r s s r r S S u u c c t t i i o o n n T T e e m m p p . . Indicates the
purge refrigerant compressor suction temperature.
It is useful for diagnosing purge system problems.
104
P P u u r r g g e e L L i i q q u u i i d d T T e e m m p p . . Indicates the temperature
sensed by the controller and used to inhibit purge
operation. The purge liquid temperature sensor,
when the chiller is operating, is the chiller saturated
condenser temperature sensor; when the chiller is
Off, it is the chiller saturated evaporator
temperature sensor. If this temperature is below the
Pumpout Inhibit Temperature that is defined in the
S S e e t t t t i i n n g g s s menu, pump-out is not allowed. This
value is used to prevent inefficient operation of the
purge under certain conditions.
C C a a r r b b o o n n T T a a n n k k T T e e m m p p . . Indicates the carbon bed
temperature and is useful for monitoring
regeneration and for diagnosing regeneration
system problems.
CVHH-SVX001G-EN