KNX
Device technology
2.2

KNX Power Supply with diagnostics, 640/320 mA, MDRC

2.2.1

Technical data

Supply
Outputs
Connections
12 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
KNX power supplies generate and
monitor the KNX system voltage (SELV).
The bus line is decoupled from the power
supply by an integrated choke.
Bus current, bus voltage, overload and
other messages can be sent via KNX for
monitoring and diagnostic purposes.
The voltage output is short-circuit and
overload protected.
Supply voltage U
s
Power consumption
- SV/S 30.320.2.1
- SV/S 30.640.5.1
Power loss
- SV/S 30.320.2.1
- SV/S 30.640.5.1
KNX voltage output I
1
Rated voltage U
N
Minimum distance between 2 SV/S in one line
Voltage output I
(SV/S 30.640.5.1 only)
2
Rated voltage U
N
Current
- SV/S 30.320.2.1
- SV/S 30.640.5.1 (total current I
Power failure buffering time
KNX
Mains voltage input
Tightening torque
The LEDs indicate the bus current
consumption and the status of the line or
device.
Device type SV/S 30.640.5.1 has an
additional 30 V DC short-circuit and
overload protected voltage output that
can be used to power an additional bus
line (in combination with a separate
choke).
100 – 240 V AC, 50/60 Hz
(85...265 V AC)
Normal operation
12.5 W
24 W
Normal operation
2.5 W
4 W
1 line with integrated choke
30 V DC +1/-2 V, SELV
200 m (KNX bus line)
without choke
30 V DC +1/-1 V, SELV
The voltage output without choke may only be
used to power an additional bus line in
combination with a separate choke.
Rated curr.
I
N
320 mA
and I
)
640 mA
1
2
200 ms
Bus connection terminal
Screw terminal
0.2...2.5 mm
2
0.2...4 mm
Maximum 0.6 Nm
Maximum
30 W
55 W
Maximum
6 W
9 W
Overload curr.
Short-circuit curr.
I
I
Ovl
Sc
0.5 A
0.8 A
0.9 A
1.4 A
2
fine-strand
solid