ABB i-bus
KNX
Device technology
Please note
ETS and the current version of the device application are required for programming.
The current version of the application is available for download at www.abb.com/knx. After import it is
available in ETS under ABB/System devices/Power Supplies.
The device does not support the password function of the KNX device in ETS. If you inhibit access to all
the project devices using a BCU code, it has no effect on this device. Data can still be read and
programmed.
Important
If the device overheats due to extended overload (> 100 °C in housing) it switches off automatically.
All LEDs are OFF. The device can be switched on again only after it has been disconnected from the
mains for 60 seconds and has cooled to operational temperature internally.
Eliminate the cause of the overload before switching back on.
When commissioning the device, ensure that the rated current is not continuously exceeded.
The voltage output without choke ( I
only be used to power an additional bus line in combination with a separate choke. It may not, for
example, be used to power IP devices.
Devices are designed for continuous operation. They are not approved for frequent switching on and off.
14 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
) is not electrically isolated from the KNX voltage output (I
2
). It may
1

Hide quick links: