B2. Hazardous Locations Certifications

Hazardous location certifications

Refer to product label for applicable approvals.
AGENCY
TYPE OF PROTECTION
Intrinsically Safe:
Class I; Division 1; Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1; T4
Class I, Zone 0 AEx ia IIC T4 Ga
Class I Zone 2 AEx ic IIC T4 Gc
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
Non Incendive:
Class I; Division 2; Groups A, B, C, D;
Class II, Division 2, Groups E, F, G;
Class III, Division 2, T6...T4
Ex nA [ia] IIC T6...T4 Gc [Ga]
CSA
Class I, Zn 2[0], AEx nA[ia] IIC T6...T4 Gc[Ga]
Explosion-Proof/ Flameproof/Dust Proof:
Class I, Division 1; Groups A, B, C, D;
(USA and
Class II, Division 1, Groups E, F, G;
Canada)
Class III, Division 1; T6...T4
Ex db[ia] IIC T6...T4 Gb[Ga]
Ex tb[ia] IIIC T95...T125 Db[Da]
Class I, Zn 1[0] AEx db [ia] IIC T6...T4
Class II, Zn 21, AEx tb[ia] IIIC T95...T125 Db[Da]
Enclosure: Type 4X/ IP66/ IP67
Standards Used:
CSA C22.2 No. 0-10
CSA C22.2 No.94.2-15
CSA C22.2 No.213-16
CAN/CSA C22.2 No.60079-1:16
CAN/CSA C22.2 No.60079-31:15
ANSI/UL 60079-1-2015
ANSI/UL 60079-31-2015
FM 3616 – Dec 2011
ANSI/UL 50E-2015
98
Table B-2 Certifications and Approvals
CSA C22.2 No.25-17
CAN/CSA C22.2 No.61010-1-12
CAN/CSA C22.2 No.60529:16
CAN/CSA C22.2 No.60079-11:14
ANSI/ISA 12.12.01-2015
ANSI/UL 60079-11-2014
FM 3600 – Dec 2011
ANSI/IEC 60529 – 2004
ANSI/UL 61010-1-2016
SmartLine Wireless User's Manual
Ambient
Product
Temperature
Applicability
Pressure
See tables below
Pressure
See tables below
Pressure
See tables below
CSA C22.2 No.30-M1986
CAN/CSA C22.2 No.157-92
CAN/CSA C22.2 No.60079-0:15
CAN/CSA C22.2 No.60079-15:16
ANSI/UL 60079-0-2013
ANSI/UL 60079-15-2013
FM 3615 – Aug 2006
ANSI/UL 913-2015