5. Wiring Instructions

Warning: this procedure can be done just by specialized personnel.
CD3000M unit has isolated heatsink. For safety connect the heatsink to hearth using its terminal
with hearth symbol.
CD3000M can be susceptible to airborne interferences from near equipment or from interferences
on main supply, so a number of precautions must be taken.
• Contactors coils and chokes must have in parallel a RC filter and must be supplied with a
different voltage line.
• All input/output signal must use screened bifilar wires.
• Signal input and output must not routing in same cable try and must not be parallel.
• Local regulations regarding electrical installation should be rigidly observed.
3.3.2 Auxiliary terminals
Before connect or disconnect, make sure that the power, control cables and wires are
insulated from the voltage.
Terminal
1
-
2
+
3
4
5
+
6
-
A2+
+
A1-
-
7
8
9
10
11
12
13
14
15
16
17
18
5.1.1 Power Terminals
Before connect or disconnect, make sure that the power, control cables and wires are
insulated from the voltage
Terminal
L1
Line Input
T1
Load Output
www.honeywell.com/imc
CD3200 up to110A
External Calibration command 24Vdc max
External Calibration command 24Vdc max
Reset
Reset
Output Command signal to CD3200 (Internal Connections)
Output Command signal to CD3200 (Internal Connections)
Input command signal 4÷20mA, 0÷10V
Input command signal 4÷20mA, 0÷10V
RS485 A
RS485 B
Output +8Vdc stabilized 1mA MAX potentiometer power supply
Common relay H.B. alarm
NC/NO H.B. relay alarm
External Current Profile
CT input with H.B. option
CT input with H.B. option
Nc not connected
Auxiliary supply voltage 240-440Vac
Ground
Auxiliary supply voltage 240-440Vac
Description
Description
12
User's Manual ver. 2.0