Technical Specifications - Honeywell CD3200 User Manual

Thyristor unit, up to 110a
Table of Contents

Advertisement

Honeywell

2. Technical specifications

2.1 General Features:
Operating temperature
Voltage power supply
Input signal
Firing mode
Auxiliary voltage supply
Fan voltage supply
Heater break alarm
Feedback
Serial communication
Mounting
Protection
www.honeywell.com/imc
CD3200 up to110A
0÷40°C for higher temperature see derating curve
24V minimum, 480V max and 600V on request
SSR
4÷20mA
0÷10V
potentiometer (10k ohm)
customer configurable with automatic zero/span calibration
One of these firing modes can be configured on line via serial port
Phase Angle + Current Limit (PA)
Soft Start + Phase Angle + Current Limit (S + PA)
230V ±15%; 10VA power consumption
440V ±15%; 10VA power consumption
230V ±15%;
110V ±15%; on request
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors.
Latching alarm plus reset. Relay output 0,5A at 125V
Voltage feedbak (V)
Square Voltage feedbak (V²)
Power feedback (VxI) (option)
RS485 Modbus protocol (option)
Din rail mounting up to 45A
Bulk head over 45A
IP20
6
User's Manual ver. 2.0