10.3.10 Current Limit
Command from current limit pot.
Operations: Read
Meaning:
It represents a value in points (0-255, 0-FF Hex) and it's the power demand in % of controller.
Example:
0%
= 0
50%
= 128
100%
= 255
Command via RS485
Operations: Read/Write
Meaning:
It's a value in points (0-255, 0-FF Hex)
It's the power set point setted in thirst buffer
Example:
0%
= 0
50%
= 128
100%
= 255
10.3.11 Status Table
Bit
Meaning
0
Short circuit on SCR
1
Load Failure
2
On-Off
3
HB Calibration in progress
4
Current Limit Flag
5
Termal
10.3.12Short circuit on SCR
Operations: Read
Meaning:
It's a bit indicating when the thyristor is in short circuit.
0
= OK
1
= Short circuit
10.3.13 Load Failure
Operations: Read
Meaning:
It's a bit indicating the partial or total load failure.
0
= OK
1
= Load failure
CD3200 up to110A
0 (Hex)
80 (Hex)
FF (Hex)
0 (Hex)
80 (Hex)
FF (Hex)
Notes
Read only
Read only
Read only
Read only
0=Normal
Read only
0=Normal
Read only