SATRON VC Optical Consistency Transmitter

3. USER GUIDE FOR MENUS

The user interface for the series VO analyzers, housing option
N, consists of display and operating keys. Among other things,
the user interface allows you to set process variables in the
desired units on the display and to confi gure the analyzer e.g.
by setting the lower and upper range-values.
In addition, you can perform diagnostic routines and view de-
vice information through the user interface.
The 8-character liquid crystal display (LCD) with backlight
allows you to display information with letters and num-
bers.
OPERATING KEYS:
With the UP/DOWN arrow keys and the ENTER and ESC you
can move in the menus.
ENTER:
Press ENTER to move to a lower level in a menu or to accept a
command or parameter value.
UP:
Use the UP arrow key to move up on the current menu level or
to increase the selected parameter value.
DOWN:
Use the DOWN arrow key to move down on the current menu
level or to decrease the selected parameter value.
ESC:
Press the ESC to move back towards the top of the main menu
or cancel the current action.
3.0 MEASUREMENTS VALUES MENU:
When the analyzer is powered up, it immediately shows the
MEASUREMENT VALUES.
Use the UP/DOWN keys to move in the menu. The menu does
not have any variables adjustable by the user.
Pressing DOWN shows you the following parameters in order.
the user calibrated information (% Cs)
the value of the fi rst mA loop
the temperature of the sensor head
the temperature of the electronics
active recipe name
Under the main menu are 6 submenus: Confi guration, New
Sample, Calibration, Diagnostics and Advanced. To enter these
submenus press ESC for 3 seconds.
3.1 Confi guration
The transmitter confi guration settings
RCP SEL
Active recipe selection menu.
RECIPE 1
Recipe selected options RECIPE (1 ... 4).
The basic factory tuning is stored in the recipe 1.
To perform a new calibration is recommended to
use a new recipe.
MAOUTPUT
The current output (mA circuit) settings.
LRV
Lower range value (4 mA)
URV
Upper range value (20 mA)
v
val
v
al
alue
DAMPING:
Time constant, in seconds for output damping. The
range is 0.000s to 60s. Set the value with the UP/DOWN
keys and accept it with ENTER or press ESC if you do
not want to change the value.
AVERAGE:
Time constant in Hz for averaging the output. The range
is 1Hz to 50Hz. . Set the value with the UP/DOWN keys
and accept it with ENTER or press ESC if you do not
want to change the value.
ALARMTYP:
The alarm current (3,7 mA or 22,5 mA).
SYSTEM CONFIGURATION
(confi gure parameters that have an effect on the system like
e.g. language and date.)
TAG:
Tag code. You can enter free-format text one character
at a time. When you select this option with ENTER the
cursor will be at the left. Select characters with ENTER
(to the right) and ESC (to the left). You can view the se-
lectable characters one character at a time with the UP/
DOWN keys until the desired character is found. When
the cursor is at the right edge you can go back to the
SYSTCONF menu either by accepting the new tag code
with ENTER or by pressing exiting without changing the
tag code by pressing the ESC key when asked to accept
your entry. Apostrophe indicates the cursor position; at
point, however, the cursor will disappear. A great deal
of special characters are available besides letters and
numbes.