Agency Compliance; Ce Requirements - Allen-Bradley Kinetix 300 User Manual

Ethernet/ip indexing servo drives
Table of Contents

Advertisement

Agency Compliance

If this product is installed within the European Union and has the CE mark, the
following regulations apply.
ATTENTION: Meeting CE requires a grounded system, and the method of
grounding the AC line filter and drive must match. Failure to do this renders the
filter ineffective and may cause damage to the filter.
For grounding examples, see
page
64.
For more information on electrical noise reduction, see the System Design for
Control of Electrical Noise Reference Manual, publication GMC-RM001.

CE Requirements

To meet CE requirements, these requirements apply:
• Install an AC line filter (Bulletin 2090 or 2097) as close to the drive as
possible.
• Use 2090 series motor power cables or use connector kits and terminate
the cable shields to the subpanel with clamp provided.
• Use 2090 series motor feedback cables or use connector kits and properly
terminate the feedback cable shield. Drive-to-motor power and feedback
cables must not exceed 20 m (65.6 ft).
• Install the Kinetix 300 system inside an enclosure. Run input power wiring
in conduit (grounded to the enclosure) outside of the enclosure. Separate
signal and power cables.
• Segregate input power wiring and motor power cables from control wiring
and motor feedback cables. Use shielded cable for power wiring and
provide a grounded 360° clamp termination.
See Appendix A on
page 171
wiring and drive/motor interconnect diagrams.
Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
Grounding Your Kinetix 300 Drive System
for interconnect diagrams, including input power
Start
Chapter 1
on
17