Agency Compliance

16
If this product is installed within the European Union and has the CE
marking, the following regulations apply.
ATTENTION: Meeting CE requires a grounded system. The method of
grounding the AC line filter and drive must match. Failure to do this renders
the filter ineffective and can cause damage to the filter.
For grounding examples, see
page
58.
For more information on electrical noise reduction, see the System Design for
Control of Electrical Noise Reference Manual, publication GMC-RM001.

CE Requirements

To meet CE requirements, these requirements apply:
• Install an AC line filter (Bulletin 2090 or 2097) as close to the drive as
possible.
• Use 2090 series motor power cables or use connector kits and terminate
the cable shields to the subpanel with clamp provided.
• Use 2090 series motor feedback cables or use connector kits and
properly terminate the feedback cable shield. Drive-to-motor power and
feedback cables must not exceed 20 m (65.6 ft).
• Install the Kinetix 350 system inside an enclosure. Run input power
wiring in conduit (grounded to the enclosure) outside of the enclosure.
Separate signal and power cables.
• Segregate input power wiring and motor power cables from control
wiring and motor feedback cables. Use shielded cable for power wiring
and provide a grounded 360° clamp termination.
See Appendix A on
page 129
wiring and drive/motor interconnect diagrams.
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Grounding Your Kinetix 350 Drive System
for interconnect diagrams, including input power
on