Electrical Connection; Connection Versions - E+E Elektronik EE23 Operation Manual

Humidity/temperature sensor
Hide thumbs Also See for EE23:
Table of Contents

Advertisement

For applications where condensation is likely to happen, certain ways of mounting are required.
• For probe hanging onto its cable from the ceiling, use the drip water protection HA010503 (not inclu-
ded in the scope of supply, see "spare parts / accessories"). This protects the probe and the sensing
head against water dripping along the cable.
• For horizontal mounted probe, a drip water point should be made just before the probe.
horizontal
Fig. 9
Mounting the sensing probe
4.3

Electrical Connection

Power supply
Fig. 10
Connection diagram
4.4

Connection Versions

standard
1) Two M16x1.5 cable glands (one of them mounted onto the enclosure)
2) Power supply + analogue outputs: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7)
3) Analogue output: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7)
4) AC power supply: cable connector, 3-poles, straight (7/8ʺ-16UN)
12
stainless steel
mounting flange
drip water loop
output and supply
Power supply and outputs
option E4
drip water
protection
hanging onto the probe cable
alarm output
Alarm output
Relais status for
RH < threshold
option AM3
Operating manual EE23 humidity / temperature sensor