ESIE15-08B
|
Part 2. Troubleshooting
4.1.2. Resistance check
1.
Measure the backup heater resistance (tolerance = ±10%).
3 kW
1~ 230 V
52.9 Ω
K1M/1
K5M/13
∞
K1M/3
∞
K1M/5
26.5 Ω
K1M/3
K1M/5
∞
K2M/1
K5M/13
∞
K2M/3
∞
K2M/5
52.9 Ω
K2M/3
K2M/5
∞
K1M/5
K2M/1
4.1.3. Isolation check
1.
Switch off the Daikin Altherma Monobloc CA via the user interface.
2.
Switch off the Daikin Altherma Monobloc CA with the field supplied circuit breaker.
C
AUTION
To prevent damage to the unit, F1B or F2B, K1M, K2M and K5M (if installed) must be OPENED before using a Meg-
ger.
3.
Open circuit breakers K1M & K2M, K5M (if installed).
4.
Set the Megger voltage to 500 VAC.
C
AUTION
Do not connect the Megger ground test lead to a another grounding wire.
5.
Connect the Megger ground test lead directly to the backup heater ground wire (see red arrow below).
19/07/16
Daikin Altherma Monobloc CA
6 kW
6 kW
9 kW
1~ 230 V
3N~ 400 V
3N~ 400 V
52.9 Ω
∞
∞
105.8 Ω
∞
105.8 Ω
26.5 Ω
105.8 Ω
26.5 Ω
∞
∞
52.9 Ω
∞
52.9 Ω
52.9 Ω
52.9 Ω
∞
∞
4. Component checklist - Water Circuit
∞
105.8 Ω
105.8 Ω
105.8 Ω
∞
52.9 Ω
52.9 Ω
52.9 Ω
∞