[32]-[35] increment the flashing digit with the button
desired function is displayed enter it with the button
display the desired function in the function display.
If the process times out the display will return "RUN" Mode.
To return to function [70] press two buttons
for a few seconds.
6.4.1 Function [31]
The zone enable function is used to enable/disable any or all of the
zones individually. If all of the zones are disabled then zone one will
remain enabled by default
In function [31] the function display will show 31, the zone display will
show 1, and the upper display will be blank.
If the zone display is flashing it indicates that the current zone is dis-
abled.
To toggle between enable and disable use the button
To advance to next zone use the button
To save the settings and return to function [71] use the button
6.4.2 Function [32]
The password enable function turns on/off the password protection for
changing the settings for the unit. In function [32] the function display
will show 32, the zone display will be blank, and the upper display will
flash 0 or 1.
If the display is 0 it indicates that the password is disabled.
If the display is 1 it indicates that the password is enabled.
To toggle between enable and disable use the button
To save setting and return to function [71] use the button
6.4.3 Function [33]
The select model function sets the type of unit for alarms, relay, degrees
C or F, control mode, and thermocouple as per the table. In function
[33] the function display will show 33, the zone display will be blank,
and the upper display will show a 4 digit model code, digit 1 will be
flashing.
27
When the
This will
and
together
zone enable
password enable
select model
To increment the flashing digit use the button
To advance to the next digit use the button
To save the settings and return to function [71] use the button
Four digit model code
Digit 1
Alarm
Type
Digit 2
Relay
And °C or °F 2 = Non Latching °C
Digit 3
CONTROL
MODE
Digit 4
T/C TYPE
Example:
To select "RAMP AND SOAK 1" With type 'K' thermocouple °F
with Non Latching HI-LO Alarm, set MODEL as shown below.
2
3
HI-LO Alarm
Non Latching °F
28
0 = Overheat Alarm
1 = Underheat Alarm
2 = HI-LO Alarm
3 = No Alarm
0 = Latching Rel. °C
1 = Latching Rel. °F
3 = Non Latching °F
0 = STANDARD CONTROL
1 = RAMP AND SOAK 1
2 = RAMP AND SOAK 2
0 = TYPE B
1 = TYPE C
2 = TYPE E
3 = TYPE J
4 = TYPE K
5 = TYPE R
6 = TYPE S
7 = TYPE T
1 4
TYPE K
RAMP AND SOAK 1