9.
Verify that the Log Service page displays, which indicates a successful login.
Note: After some idle time, the Web Console will time out. If this occurs, the user
will need to return to the main page to log back into the console. Session
timeout does not automatically redirect the console back to the login
page.

4.3.3. Configure the Network

4.3.3.1.
EFA IP Addresses
By default, the Embedded Field Agent's WAN interface is set to a static address of
172.31.0.100 with a subnet mask of 255.255.0.0.
To change the WAN IP address
1.
Verify that the WAN Ethernet cable is connected to the IICS Cloud port / EFA Port.
If a network proxy is needed to connect the field agent to the WAN, refer to the
section
Configure a Network
2.
From the Web Console, navigate to the Technician Console, Network
Configuration page.
GFK-3002A
Proxy.
October 2017
20