4.4

Extended module configuration

Table 4-2
Address
Name
0 . 0
NR0001.BGNR
2 . 0
NR0001.Kanal
4 . 0
NR0001.S5_Typ
10 . 0
NR0002.BGNR
12 . 0
NR0002.Kanal
14 . 0
NR0002.S5_Typ
20 . 0
NR0003.BGNR
22 . 0
NR0003.Kanal
24 . 0
NR0003.S5_Typ
30 . 0
NR0004.BGNR
32 . 0
NR0004.Kanal
34 . 0
NR0004.S5_Typ
40 . 0
NR0005.BGNR
42 . 0
NR0005.Kanal
44 . 0
NR0005.S5_Typ
50 . 0
NR0006.BGNR
52 . 0
NR0006.Kanal
54 . 0
NR0006.S5_Typ
60 . 0
:
62 . 0
:
64 . 0
:
Connecting TM I/O to PCS 7
C79000-G8076-C710-04
If you specifically assign all modules to the 100-ms cycle, cycle conflict is
switched off, but the respective cycle might be overloaded in this operation.
When you choose such an "Overload configuration" (e.g. to obtain swift and
conflict-free processing as far as possible), you must nevertheless take into
account that the processing time for this cycle is increased accordingly.
In addition to transparent SIMATIC interface modules (see Table 4-3 in
Chapter 4.7), you must also configure the subordinate I/O modules. Do so by
opening DB2 in the block container of FM456-4, using the block editor.
After you select "Data view" iin the "View" menu, you can see the following
figure, for example:
Type
Start value
INT
-1
INT
0
STRING [ 4 ]
' '
INT
-1
INT
0
STRING [ 4 ]
' '
INT
-1
INT
0
STRING [ 4 ]
' '
INT
-1
INT
0
STRING [ 4 ]
' '
INT
-1
INT
0
STRING [ 4 ]
' '
INT
-1
INT
0
STRING [ 4 ]
' '
:
:
:
:
:
:
The "Name" column shows you the consecutive number of the configured S5
module.
Select the "Actual value" column. Enter the slot number of the TELEPERM
module configured in DB1 in the "Module no. of the TM module" (refer to
Table 4-1 in Chapter 4.3) row.
In the "Channel number" row, enter the byte address. Configure the S5 mo-
dule ID in the "S5 module type" row.
Actual
Comment
value
114
Module no. of the TM module
8
Channel number (Offset)
'DE2'
S5 Module type
114
Module no. of the TM module
0
Channel number (Offset)
'DA1'
S5 Module type
114
Module no. of the TM module
1
Channel number (Offset)
'DA1'
S5 Module type
114
Module no. of the TM module
2
Channel number (Offset)
'DA1'
S5 Module type
114
Module no. of the TM module
3
Channel number (Offset)
'DA1'
S5 Module type
-1
Module no. of the TM module
0
Channel number (Offset)
' '
S5 Module type
:
:
:
:
:
: