Process control system. connecting tm i/o to pcs 7
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Configuration
Configuring input
modules
Configuring output
modules
Deleting modules
in extended confi-
gurations
4-8
Channel number
NR0xxx.Kanal
S5-Module type
NR0xxx.S5_Typ='xy'
x = DI
x = AI
y = 1 ... 16
NR0xxx.Kanal
NR0xxx.S5_Typ='xy'
x = DQ
x = AQ
y = 1 ... 16
To delete the TELEPERM M slot (that is, the connection module), you must
delete the entry of the TM module in DB1 of FM456-4 and possible entries
of subordinate S5 modules in DB2 of FM456-4.
This entry specifies the byte address for the
input area of the S5 module.
Specifies the S5 module ID.
.
The entry x and y can be defined with the
following values:
Digital input modules
Analog value input module
Entry for 1 to 16 byte for digital input
or 1 to 16 channels for analog input
(corresponds with 2 to 32 bytes)
This entry specifies the byte address for the
output area of the S5 module.
Specifies the S5 module ID.
The entry x and y can be defined with the
following values:
Digital output module
Analog value output module
Entry for 1 to 16 byte for digital output
or 1 to 16 channels for analog output
(corresponds with 2 to 32 bytes)
Connecting TM I/O to PCS 7