Hardware structure
Information
1.2
Migration rack II
General
Features
1-4
For additional information on the TPM 478-2 interface modules refer to
Chapter 5 in this manual.
The migration rack II is a preassembled module rack with the dimensions of
the panel-mount system ES 902 which is required for operating a PCS7/TM
system in a TELEPERM M cabinet.
All system components such as DC power supply, CPU, FM456-4 and I/O
bus interface can be operated on the short backplane PCB.
The additional five I/O slots the migration rack II is equipped with can hold
TELEPERM M I/O modules taken from an AS 220 S-/AS 235 basic unit and
can be assigned freely to I/O bus A and B.
For the PCS7/TM system, migration rack II provides five TELEPERM M
I/O slots for the installation of TELEPERM M I/O modules taken from an
AS 220 S-/AS 235 basic unit. All slots can be operated on I/O bus A or split
up in a 3 : 2 ratio between I/O bus A and B.
Other features are the simplified wiring (supply and process control messa-
ges) and the possibility of replacing certain mechanical components (connec-
tors) in case of error.
The wiring features no loose ends, that is, installation technique is adapted to
AS 230/235.
The integrated backplane also provides distribution of specific signals and
voltages. Process control monitoring signals are now terminated on the back-
plane terminal blocks - same as in the AS 235. The existing cabinet wiring
can be used almost completely.
The front panel fuses for L+ (16A) and PM (4A) can be replaced from the
front in case of error. Due to the fastening mechanism on the side, the I/O bus
connectors can be replaced in case of error without having to remove the mi-
gration rack.
The migration rack is equipped with by-pass capacitors for the L+, PM, M24
and MZ voltages for the derivation of electrical disturbance to the shielding
and, thus to the metal case.
All position addresses of the slots are equipped with filters.