Migration rack II
6.5

Operating conditions

PCS7/TM with
TELEPERM M I/O:
Special notes:
Expansion units
CP 581-TM
LED
6-14
You can use all TELEPERM I/O modules listed in "Supplementary System
Documentation AS 388/TM and AS 488/TM", Order No.
C79000-G8076-C700, Catalog PLT 112 and those published on the Intranet/
Internet TELEPERM M site.
Migration rack II, together with TPM 478-2, is approved for operation with
up to seven expansion units (3 in the basic cabinet, 4 for in the expansion
cabinet). The ribbon cable must be adapted as required.
If you include 1 to 4 ES 100 K per I/O bus, the max. number of addressable
I/O module racks is 2 x 4 EU/ES.
The module CP 581-TM can only be operated on a PCS7/TM in combination
with S5Kx drivers.
You can operate only one module of the type CP 581-TM per configuration
(migration rack plus basic cabinet plus expansion cabinet) (5-V supply condi-
tion). You cannot operate an additional N.V-24.
Errors/failures/disturbances of the I/O bus system are not indicated by LEDs
on TPM 478-2. This can be recognized, for example, on driver failure
messages.
Connecting TM I/O to PCS 7
C79000-G8076-C710-04