Siemens SIMATIC PCS 7 Manual page 28

Process control system. connecting tm i/o to pcs 7
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Configuration
M7-SYS
Blocks
System SW
4-4
S
call SIMATIC Manager
• open the current project
• select the M7 program of the FM456-4
• PLC ³ Manage M7 target system ...
• select the medium "Memory Card"
• select the "Install OS" tab
• select ³ install "M7 RMOS32"(confirm all prompts)
å the Memory Card is formatted, M7-SYS will be installed.
S
PLC ³ Manage M7 target system ...
• select the medium "Memory Card"
• select the "Programs" tab
• select ³ install "Blocks" (when prompted to write batch files to
\etc\inittab, confirm with "Yes")
å the HW configuration, configured connections and configuration
DBs are now copied.
Since the system software is not visible in SIMATIC Manager when the op-
tional package M7-ProC/C++ has not been installed, the system SW and all
its components must be copied to Memory Card, using Windows Explorer:
• select the catalog \Siemens\Step7\S7libs\Pcs7_tm\hrs\P0000002\
• copy the file TM_EA_S7.EXE to mc:\romdir
• create a new catalog mc:\S7auto on Memory Card
• copy the file TM_EA_S7.BAT to mc:\S7auto
• copy the file BGRLISTE.TYP to mc:\romdir
• edit the file mc:\etc\inittab:
At the end of the file in block "Init 2 - not synchronized user ..."
enter the line:
2 \s7auto\tm_ea_s7.bat
Connecting TM I/O to PCS 7
C79000-G8076-C710-04