7. General Operation
Below is the setting range for User-Def. You may change the limit manually by using
this function.
Solis-20K/Solis-25K/Solis-30K/Solis-30K-HE /Solis-36K-HV/Solis-40K-HV
OV-G-V1: 410---530V
OV-G-V1-T: 0.1---9S
OV-G-V2: 430---580V
OV-G-V2-T: 0.1---1S
UN-G-V1: 300---360V
UN-G-V1-T: 0.1---9S
UN-G-V2: 230---330V
UN-G-V2-T: 0.1---1S
Save/Cancel
Y E S = < E N T > N O = < E S C >
Figure 7.26 Save / cancel
NOTE:
The initial value of the User-Def standard are for reference only. It does
not represents the correct value suitable for use.
Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the
highlighted item. Press the UP/DOWN key again to change the setting. Press the
ENTER key to save the setting. Press the ESC key to cancel the change and return
to the previous menu.
.38.
OV-G-F1: 50.2-53Hz(60.2-63Hz)
OV-G-F1-T: 0.1---9S
OV-G-F2: 51-53Hz(61-63Hz)
OV-G-F2-T: 0.1---9S
UN-G-F1: 47-49.5Hz(57-59.5Hz)
UN-G-F1-T: 0.1---9S
UN-G-F2: 47-49Hz(57-59Hz)
UN-G-F2-T: 0.1---9S
2015-02-23 19 35
Save & Send
Cancel & Exit
7. General Operation
7.5.2 Grid ON/OFF
This function is used to start or stop the generation of the inverter (see Figure 7.27).
Grid ON/OFF
Y E S = < E N T > N O = < E S C >
Figure 7.27 Set Grid ON/OFF
Press the DOWN key to move the cursor, Press the UP key to revise the value.
Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.
7.5.3 Power Setting
Active and reactive power can be set through power setting button.
Power Control
Output Power Control
Reactive Power Control
Output Power Cortrol With Restore
Reactive Power Control With Restore
Figure 7.28 Power setting
2015-02-23 19 35
Grid ON
Grid OFF
2015-02-23 19 35
.39.