Dimensions and weights

H1 height with gland box, H2 height without gland box.
Frame
size
H1
in.
R2
15.96
R3
18.54
R4
23.87
R5
29.09
R6
34.65

UL/CSA markings

The ACS800-01 and ACS800-U1 units of UL type 1 are C-UL US listed and CSA marked. The UL and
CSA markings are pending for units of UL type 12.
UL
The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical
amperes at the drive nominal voltage (600 V maximum for 690 V units).
The drive provides overload protection in accordance with the National Electrical Code (US). See
ACS800 Firmware Manual for setting. Default setting is off, must be activated at start-up.
The drives are to be used in a heated indoor controlled environment. See section
for specific limits.
Brake chopper - ABB has brake choppers that, when applied with appropriately sized brake resistors,
will allow the drive to dissipate regenerative energy (normally associated with quickly decelerating a
motor). Proper application of the brake chopper is defined in chapter
applied to a single drive or multiple drives with DC bus connected to allow a sharing of regenerative
energy.
UL type 1
H2
Width
Depth
in.
in.
14.57
6.50
16.54
6.81
10.45
19.29
9.45
10.79
23.70
10.43
11.26
27.56
11.81
15.75
Weight
Height
in.
lb
in.
8.89
20
20.78
31
20.78
57
30.49
75
30.49
148
36.34
UL type 12
Width
Depth
in.
in.
10.35
9.49
10.35
10.74
14.84
10.94
14.84
12.14
16.52
16.54
Ambient conditions
Resistor
braking. This can be
Technical data
95
Weight
lb
34
41
73
112
170