BJM Pumps® KZN Series submersible pump. This manual also contains information to optimize performance and longevity of your BJM Pumps submersible pump. The submersible KZN Series pumps are designed to pump water and water based slurries.
SAFETY Pump installations are seldom identical. Each installation and application can vary due to many different factors. It is the owner/service mechanics responsibility to repair, service, and test to ensure that the pump integrity is not compromised according to this manual.
INSPECTION Review all safety information before servicing pump. The following are recommended installation practices/procedures for the pump. If there are questions in regards to your specific application, contact your local BJM Pumps distributor or BJM Pumps, LLC. PRE-INSTALLATION INSPECTION 1) Check the pump for damage that may have occurred during shipment.
BJM Pumps, LLC at 860-399-5937. As a general rule, KZN Series top discharge pumps can pump down to a level above the suction screen. Pumping lower than screen will permit air to enter the pump and cavitate, lose prime or become air bound.
Page 8
1. By looking at the impeller; the rotation of the impeller should be counter clockwise as shown in the picture below. 2. By looking from the top of the pump. Since the impeller cannot be seen, the best way to check the rotation is to check the kick back motion of the pump when the pump just starts.
PUMP OPERATION This pump is designed to handle dirty water that contains some solids. It is not designed to pump volatile or flammable liquids. Do not attempt to pump any liquids which may damage the pump or endanger personnel as a result of pump failure.
Typical 3 phase manual control 1 TYPICAL AUTOMATIC DEWATERING INSTALLATION NOTE: Maximum recommended starts should not exceed 10 times per hour. Float switches (wired into the pump motor or piggy-back style) are available from the factory as an option. Note: 208V, 230V, 460V & 575V pumps do not have a plug installed. Three phase pumps need a separate control box with float(s) for automatic operation.
STOPPING To stop the pump (manual and automatic mode), unplug it from the power source, turn off the breaker, or turn the power source off (generator).
“UTILLISER UN DÉMARREAR APPROUVÉ CONVENANT AU COURANT Á PLEINE CHARGE DU MOTEUR.” BJM Pumps submersible pumps have been evaluated for use with water or water based solutions. Please contact the manufacturer for additional information. THREE PHASE WIRING INSTRUCTION FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING.
Page 13
Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician. To automatically operate a non-automatic three phase pump, a control panel is required. Follow the instructions provided with the panel to wire the system. automatic three phase pumps see automatic three phase wiring diagram.
Pump should be disconnected from the electric power supply before proceeding to do any service or maintenance. To service or repair your pump, please contact your local BJM Pumps distributor. Service should only be performed by a qualified electrician. MAINTAINING YOUR PUMP ...
More frequent inspections are required if the pump is used in a harsh environment. Preventative maintenance should be performed to reduce the chance of premature failure. Worn impellers and lip seals should be replaced. Cut or cracked power cords must be replaced. (Never operate a pump with a cut, cracked or damaged power cord.) ...
21) Fill with recommended new oil. 22) Replace the oil inspection bolt o-ring. 23) Secure the oil inspection bolt. *Note: If there is excessive liquid found in the oil or mechanical seal damaged, please contact BJM Pumps authorized service centers.
BJM Pumps, LLC’s liability for any breach of this warranty shall be limited solely to replacement or repair, at the sole option of BJM Pumps, LLC, of any part or parts of the Product found to be defective during the warranty period, provided the Product is properly installed and is being used as originally intended.
START-UP REPORT FORM This form is designed to record the initial installation, and to serve as a guide for troubleshooting at a later date (if needed). BJM Pumps, LLC 123 Spencer Plain Road Old Saybrook, CT. 06475 Pump Owner’s Name...
Page 31
START-UP REPORT FORM presence? Are guide rails exactly vertical? Is base elbow installed level? Liquid level controls: Model control installed away from turbulence? Operation Check Tip lowest float (stop float), all pumps should remain off. Tip second float (and stop float), one pump comes on. Tip third float (and stop float), both pumps on (alarm on simplex).
Page 32
START-UP REPORT FORM Voltage supply at panel line connection, pump on L1-L2 L2-L3 L3-L1 Amperage load connection, pump on FINAL CHECK Is pump secured properly? Was pump checked for leaks? Do check valves operate properly? Flow: Does station appear to operate at proper rate? Noise level: Acceptable...