Environmental Conditions - Siemens REV23RF16A User Manual

Self-learning room temperature controller receiver
Table of Contents

Advertisement

Important:
Technical data controller / transmitter REV23RF
General data
controller / transmitter
General data controller
General data transmitter
Environmental
conditions
Siemens Building Technologies
HVAC Products
k)
The ON / OFF signal will then be repeated every 20 minutes (the 20-minute in-
terval has been chosen to extend battery life)
l)
Reset the setpoint according to f) and g)
m) Press
to reset the operating mode to the required position
The receiver's readiness to learn is a maximum of 25 minutes. If no signal is received
from the transmitter during that period of time, repeat steps d) through m) above.
The control mode can be changed via the menu-driven heating engineer settings.
If the room temperature displayed does not agree with the room temperature effectively
measured, the temperature sensor should be recalibrated (refer to «Calibration of sen-
sors»).
Operating voltage
Batteries (alkaline AA)
Battery life
Backup for battery change
Sensing element NTC
Measuring range
Time constant
Setpoint setting ranges
Normal temperature
Economy temperature
Frost protection setpoint
Setting range
Factory setting
Resolutions of settings and display
Setpoints
Switching times
Measurement of actual value
Display of actual value
Display of time
SRD band
Transmit frequency REV23RF
Max. transmitter power
Max. data throughput
Modulation
Frequency stability
Address range
(preset in the factory)
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Room Temperature Controller REV23RF16A/SET
DC 3 V
2 x 1.5 V
approx. 2 years
max. 1 min
NTC 10 k
at 25 °C ±1 %
0...50 °C
max. 10 min
5 ... 29 °C
5 ... 29 °C
5...29 °C
5 °C
0.2 °C
10 min
0.1 °C
0.2 °C
1 min
868.7 to 869.2 MHz
868.95 MHz
< 10 mW / typically 4 mW
19200 symbol/s = 38400 Bit/s
binary frequency changeover BFSK
±
±
<
20 ppm (
17 kHz)
16 Bit (0...65535)
to IEC 60 721-3
class 3K3
5 ...+ 4 0 °C
< 85 % r. h.
to IEC 60 721-3
class 2K3
25...+70 °C
< 93 % r. h.
class 2M2
11/16
CE1N2269en
09.10.2003

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rev23rfRev-r.02/16a

Table of Contents