V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS

INSTALLATION

When Installing This Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard can cause property
damage, severe-injury or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after completion of installation.
3. Do not attempt to use a control set for natural
(manufactured) gas on LP gas, or a control set
for LP on natural (manufactured) gas.
4. Do not bend pilot tubing at control or pilot after
compression nut has been tightened, or gas
leakage at the connection may result.
5. Always install sediment trap in gas supply line
to prevent contamination of gas control.
6. Do not force the gas control knob. Use only
your hand to push down the reset button or turn
the gas control knob. Never use any tools. If the
knob or reset button will not operate by hand,
the control should be replaced by a qualified
service technician. Force or attempted repair
may result in fire or explosion.
CAUTION
Never apply a jumper across or short the valve
coil terminals. This may burn out the heat
anticipator in the thermostat.
IMPORTANT
These gas controls are shipped with protective
seals over inlet and outlet tappings. Do not
remove seals until ready to connect piping.
Follow the appliance manufacturer's instructions if
available; otherwise, use the instructions provided below
as a guide.
69-0422—03
Convert between Natural and LP
Gas
WARNING
Fire or Explosion Hazard can cause property
damage, severe-injury or death.
Do not attempt to use a control set for natural
(manufactured) gas on LP gas, or a control set
for LP on natural (manufactured) gas.
To convert a control from natural gas to LP gas, or from
LP gas to natural gas, contact your Honeywell
representative.

Install Adapters to Control

If adapters are to be installed on the gas control, mount
them as follows:
Flanges:
1. Choose the appropriate flanges for your application.
NOTE: A right angle inlet flange cannot be used with
ECO connected.
2. Remove seal over control inlet or outlet.
3. Check to ensure that the O-ring is fitted in the
groove of flange. If the O-ring is not attached or is
missing, do not use the flange.
4. With O-ring facing valve, line up the screw holes on
the control with the holes in the flange. Insert and
tighten the screws provided with the flange (See
Fig. 1). Tighten the screws to 25 in.-lbs
(2.8 N·m) of torque to provide a gas-tight seal.
Bushings:
1. Remove seal over control inlet and outlet.
2. Apply moderate amount of good quality pipe
compound to bushing, leaving two end threads
bare. On LP installation, use compound resistant to
LP gas. Do NOT use Teflon™ tape.
3. Insert bushing in control and thread pipe carefully
into bushing until tight.
GAS CONTROL OUTLET
FLANGE
9/64 INCH HEX SCREWS (4)
1
DO NOT OVERTIGHTEN SCREWS.
TIGHTEN TO 25 INCH-POUNDS.
Fig. 1. Fasten Flange to Valve with 25 in.- lbs
(2.8 N·m) Torque.
2
®
1
M2913A