Metro Cell installation and commissioning
....................................................................................................................................................................................................................................
Connect the ground cable
Note: The grounding of the device depends on customer, country and site
requirements, therefore these should be checked beforehand.
The Metro Cell Indoor must be grounded with a 16 mm² ground cable (Type
NYY-1x16mm² or similar) to a grounding system. The grounding cable and cable lug
are not included in delivery and must be locally supplied.
To attach the ground cable perform the following steps.
...................................................................................................................................................................................................
Route the ground cable from the ground system to the Metro Cell - Indoor.
1
...................................................................................................................................................................................................
At the Metro Cell - Indoor cut the cable to a proper length, strip the cable end and crimp a
2
ground lug, with a hole suitable for an M6 screw, on the end of the cable.
Clean the contact surface area and use antioxidant to avoid oxidation.
...................................................................................................................................................................................................
3
Connect the ground cable to the grounding point on the Metro Cell - Indoor.
....................................................................................................................................................................................................................................