change the language, press the OK key and use the Y
and B keys to scroll to the desired language and then
press OK.
Select language
[0] English
SETUP 1
Status
Menu
Com.
On
Warn.
Alarm
Hand
On
Fig. 62 - - Keypad with Power Up Screen Displayed
2. Selecting Regional Settings:
a. Press the Off Reset key.
b. Press the Menu key to move the B(triangle
icon) so it is positioned over Main Menu. The
display show the following - -
0--- ** Operation / Display
1--- ** Load and Motor
c. Press the OK key, the display changes to - -
0--- 0* Basic Settings
0--- 1* Set--- up Operations
NOTE: Press the Back key to return to the previous display
d. With the top row highlighted, press OK. The
display changes to - -
0--- 01 Language
[0] English
e. Press B(Down Arrow key) once; the display
changes to - -
0--- 03 Regional Settings
[0] International
f. Press OK; the [0] is now highlighted.
g. Press B(Down Arrow) key once; the display
changes to - -
0--- 03 Regional Settings
[1] North America
h. Press OK
NOTE: If the Alarm 060 appears, follow Step 3 to clear
the alarm. Make sure to press Off Reset when done. If
there is no alarm, continue at Step 4.
English
Quick
Main
Menu
Menu
OK
Off
Auto
Reset
On
3. Clearing Alarm 060: External Interlock:
a. Press the Menu key twice to position the B(tri-
angle icon) over Main Menu; the display
changes to - -
b. Press the B(Down Arrow) key until the follow-
ing display appears - -
c. Press OK. The display changes to - -
d. Press B(Down Arrow) once to highlight the bot-
tom row and press OK. The display changes to - -
C13119
e. Press B(Down Arrow) twice; the following
display appears- -
f. Press OK to highlight the number in the bracket.
g. Press B(Down Arrow) until the following display
appears - -
h. Press OK.
i. Press Off Reset. The Alarm indicator disappears.
4. Entering Grid Type:
a. Press the Menu key to move the B(triangle
icon) so it is positioned over Main Menu. The
display show the following - -
b. Press OK twice: the display changes to - -
c. Press B(Down Arrow) three times, to reach the
following display - -
d. Press OK to highlight the number in the bracket
and then use the Y and B (Up and Down
Arrow) keys to select the desired voltage and
Hertz for the unit.
e. Press OK to accept the selection and continue.
65
0--- ** Operation / Display
1--- ** Load and Motor
4--- ** Limits / Warnings
5--- ** Digital In/Out
5--- 0* Digital I/O mode
5--- 1* Digital Inputs
5--- 10 Terminal 18 Digital In...
[8] Start
5--- 12 Terminal 27 Digital In...
[7] External Interlock
5--- 12 Terminal 27 Digital In...
[0] No operation
0--- 0* Basic Settings
0--- 1* Set--- up Operations
0--- 01 Language
[0] English
0--- 06 Grid Type
[102] 200--- 240V/60Hz