Carrier WeatherExpert 48LC Installation Instructions Manual page 14

Weatherexpertr series single package rooftop gas heat/electric cooling unit with puronr (r ---410a) refrigerant sizes: 14, 17, 20, 24, 26
Hide thumbs Also See for WeatherExpert 48LC:
Table of Contents

Advertisement

C
LOCATION
DIMENSION
A
36---in (914 mm)
B
42---in (1067 mm)
18---in (457 mm)
36---in (914 mm)
C
42---in (1067 mm)
96---in (2438 mm)
D
42---in (1067 mm)
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning
overhead obstruction or for vertical clearances.
48LC**
Base Unit
Economizer
Powered Outlet
Curb
14--- in/356 mm
24--- in/610 mm
B
CONDITION
• Recommended clearance for air flow and service
• Recommended clearance for air flow and service
• No Convenience Outlet
• No Economizer
• No field --- installed disconnect on economizer hood side (Factory--- installed disconnect installed).
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically non--- conductive (e.g.: wood, fiberglass).
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically conductive (e.g.: metal, masonry).
• Economizer and/or Power Exhaust installed.
• Check for sources of flue products with 10 feet (3 meters) of economizer fresh air intake.
• Recommended clearance for service.
Fig. 5 - - Service Clearance Dimensional Drawing
Table 1 – Operating Weights
14
17
1853 (842.3)
2095 (952.3)
246 (112)
246 (112)
35 (16)
35 (16)
240 (109)
240 (109)
340 (154)
340 (154)
A
UNIT LB (KG)
20
24
2201 (1000.7)
2347 (1067.0)
246 (112)
246 (112)
35 (16)
35 (16)
255 (116)
255 (116)
355 (161)
355 (161)
14
D
26
2492 (1132.6)
246 (112)
35 (16)
273 (124)
355 (161)
C12384