Staged Air Volume (SAVt) with Variable
Frequency Drive
The Staged Air Volume (SAV) system utilizes a Variable
Frequency Drive (VFD) to automatically adjust the indoor
fan motor speed in sequence with the unit's ventilation,
cooling and heating operation. Per ASHRAE 90.1- - 2016
standard during the first stage of cooling operation the
SAV system will adjust the fan motor to provide 66% of
the design airflow rate for the unit. When the call for the
second stage of cooling is required, the SAV system will
allow the design airflow rate for the unit established
(100%). During the heating mode, the SAV system will
allow total design airflow rate (100%) operation. During
ventilation mode, the SAV system will operate the fan
motor at 66% speed.
230V/460V
575V ONLY
C13209
Fig. 57 - - VFD Location