Siemens SIM-16 Installation Instructions page 4

Supervised input module

Advertisement

NOTES
1. All inputs supervised.
2. All inputs power limited to
NFPA 70 per NEC 760.
3. Wiring for TB1 and TB2 is 18
AWG min., 12 AWG max.
4. Maximum distance 500 feet
from SIM-16 to supervised
input.
5. In the Zeus Programming
Tool, select supervised for
each supervised input.
6. Supervised and unsuper-
vised inputs may be mixed
on a single SIM-16.
Figure 5
SIM-16 Supervised Input Wiring
NOTES
1. All inputs unsupervised.
2. All inputs power limited to
NFPA 70 per NEC 760.
3. Wiring for TB1 and TB2 is 18
AWG min., 12 AWG max.
4. All inputs must remain
inside the enclosure or
within 20 feet in rigid
conduit.
5. In the Zeus Programming
Tool, select unsupervised for
each unsupervised input.
6. Supervised and unsuper-
vised inputs may be mixed
on a single SIM-16.
Figure 6
SIM-16 Unsupervised Input Wiring
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
*SUPPLIED WITH
THE SIM-16
INPUT #5
INPUT #9
CONNECTION
INPUT #5
INPUT #9
For CE applications in Cerberus E100 systems refer to
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
TYPICAL
*6.8K
CONNECTION
(16 PLACES)
1
2
3
4
5
9
10
11
12
13
SIM-16
16
15
14
13
8
7
6
5
INPUT #2
INPUT #1
TYPICAL
(16 PLACES)
1
2
3
4
5
9
10
11
12
13
SIM-16
16
15
14
13
12
8
7
6
5
4
Siemens Gebäudesicherheit
GmbH & Co. oHG
D-80930 München
INPUT #2
TB1
6
7
8
14
15
16
INPUT #6
12
11
10
9
4
3
2
1
TB2
INPUT #16
TB1
6
7
8
14
15
16
INPUT #6
11
10
9
3
2
1
TB2
INPUT #16
P/N 315-034060-3