Door Control Programming - Honeywell Galaxy Keyprox Installation And Programming Instructions

Table of Contents

Advertisement

Door Control Programming

Door control functionality can be achieved by setting up zones, outputs and links on the
Galaxy panel as shown in the example below.
Zone 1011 is programmed as a Security zone.
Zone 1012 is programmed as a Link zone.
Output 1011 is programmed as Link-A type, mode=pulse 5 Sec.
Output 1021 is programmed as Link-B (door open time out), pulse 15 Sec.
Keyprox is on address 00 (MAX 10)
Program the following links:
1.
Source MAX 10
2.
Source MAX 10
3.
Source #1012
4.
Source Zone 1012 Destination Link-A
5.
Source Zone 1012 Destination Link-B
This will program the door to unlock for 5 seconds and allow it to stay open for 15 seconds from
whenever a valid card is swiped at the Keyprox. Zone 1012 is programmed as an Egress button,
which will open the door in the same way as a valid card swipe.
If the door is forced, a standard zone alarm will occur. It will not be recorded as a MAX alarm
in the Access log (menu 25).
Destination Link-A
Destination Link-B
Destination Zone 1011
6