Siemens SED2 VFD Operating Instructions Manual page 22

Electronic bypass option
Hide thumbs Also See for SED2 VFD:
Table of Contents

Advertisement

SED2 VFD Electronic Bypass Option Operating Instructions
Table 3. Wire Sizes and Tightening Torques for Electronic Bypass System with 380V to 480V Drive.
Bypass
Part
Frame
HP
kW Amps
Number
Size
VBE30.5----
A
0.5
VBE30.7----
A
0.7
VBE31.0----
A
1.0
VBE31.5----
A
1.5
VBE32.0----
A
2.0
VBE33.0----
B
3.0
VBE35.0----
B
5.0
VBE37.5----
C
7.5
VBE310----
C
10
VBE315----
C
15
11.0
VBE320----
C
20
15.0
VBE325----
D
25
18.5
VBE330----
D
30
22.0
VBE340----
D
40
30.0
VBE350----
E
50
37.0
VBE360----
E
60
45.0
VBE375----
F
75
55.0
VBE3100----
F
100
75.0
VBE3125----
F
125
90.0
VBE3125--
F
90.0
HA
* Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac.
14
Circuit Breaker
Torque,
Wire
lb-in
Size *
(Nm)
14-10
0.37
1.1
32 (3.6)
Cu
14-10
0.55
1.6
32 (3.6)
Cu
14-10
0.75
2.1
32 (3.6)
Cu
14-10
1.1
3.0
32 (3.6)
Cu
14-10
1.5
3.4
32 (3.6)
Cu
14-10
2.2
4.8
32 (3.6)
Cu
14-10
4.0
7.6
32 (3.6)
Cu
14-10
5.5
11
32 (3.6)
Cu
14-10
7.5
14
32 (3.6)
Cu
14-10
20 - 60
21
Cu
(2.2 - 6.8)
10-1/0
20 - 60
27
Cu
(2.2 - 6.8)
10-1/0
20 - 60
34
Cu
(2.2 - 6.8)
10-1/0
20 - 60
40
Cu
(2.2 - 6.8)
10-1/0
20 - 60
52
Cu
(2.2 - 6.8)
10-1/0
20 - 60
65
Cu
(2.2 - 6.8)
3-3/0
77
80 (9)
Cu
3-3/0
96
80 (9)
Cu
6 - 350
120 - 275
124
kcmil
(14 - 31.1)
Cu
6 - 350
120 - 275
156
kcmil
(14 - 31.1)
Cu
6 - 350
120 - 275
178
kcmil
(14 - 31.1)
Cu
Disconnect
Switch
Torque,
Torque,
Wire
Wire
lb-in
Size *
Size *
(Nm)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(.8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 to17
18 - 22
18-10
14-10
(1.5 - 1.7)
(2 - 2.5)
17 - 22
18 - 22
14-8
14-10
(1.9 - 2.5)
(2 - 2.5)
17 - 22
27 - 40
14-8
18-3
(1.9 - 2.5)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
6 - 350
120 - 275
124 - 210
6-3/0
kcmil
(13.5 - 31.1)
(14 - 23.7)
6 - 350
120 - 275
124 - 210
6-3/0
kcmil
(13.5 - 31.1)
(14 - 23.7)
6 - 350
120 - 275
124 - 210
6-3/0
kcmil
(13.5 - 31.1)
(14 - 23.7)
Overload
Max
Range,
Backup
Wire
lb-in
Amps
Fuse,
Size*
(Nm)
Amps
.7 - 1.0
4
1.1 - 1.6
6
1.4 - 2.0
8
2.2 - 3.2
12
2.8 - 4
16
3.5 - 5
20
7 - 10
40
9 - 12
45
11 - 16
60
17 - 22
80
22 - 32
125
28 - 40
150
28 - 40
150
40 - 50
200
57 - 75
300
70 - 90
350
80 - 100
400
14-2/0
50 - 200
800
14-2/0
50 - 200
800
14-2/0
50 - 200
800
14-2/0
Siemens Building Technologies
Ground Lug
Torque,
lb-in
(Nm)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
14-2
35 (4)
50 (5.6)
50 (5.6)
50 (5.6)
50 (5.6)