Siemens SED2 VFD Operating Instructions Manual page 23

Electronic bypass option
Hide thumbs Also See for SED2 VFD:
Table of Contents

Advertisement

Table 4. Wire Sizes and Tightening Torques for Electronic Bypass System with 500V to 600V Drive.
Bypass
Part
Frame
HP
Number
Size
VBE40.5----
C
0.5
VBE40.7----
C
0.7
VBE41.0----
C
1.0
VBE41.5----
C
1.5
VBE42.0----
C
2.0
VBE43.0----
C
3.0
VBE45.0----
C
5.0
VBE47.5----
C
7.5
VBE410.----
C
10
VBE415.----
C
15
VBE420.----
C
20
VBE425.----
C
25
VBE430.----
D
30
VBE440.----
D
40
VBE450.----
E
50
VBE460.----
E
60
VBE475.----
F
75
VBE4100----
F
100
VBE4125----
F
125
* Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac.
Siemens Building Technologies, Inc.
Circuit Breaker
kW Amps
Torque,
Wire
lb-in
Size *
(Nm)
14-10
0.37
.9
32 (3.6)
Cu
14-10
0.55
1.3
32 (3.6)
Cu
14-10
0.75
1.4
32 (3.6)
Cu
14-10
1.1
2.1
32 (3.6)
Cu
14-10
1.5
2.7
32 (3.6)
Cu
14-10
2.2
3.9
32 (3.6)
Cu
14-10
4.0
6.1
32 (3.6)
Cu
14-10
5.5
9
32 (3.6)
Cu
14-10
7.5
11
32 (3.6)
Cu
14-10
11.0
17
32 (3.6)
Cu
10-1/0
20 - 60
15.0
22
Cu
(2.2 - 6.8)
10-1/0
20 - 60
18.5
27
Cu
(2.2 - 6.8)
10-1/0
20 - 60
22.0
32
Cu
(2.2 - 6.8)
10-1/0
20 - 60
30.0
41
Cu
(2.2 - 6.8)
10-1/0
20 - 60
37.0
52
Cu
(2.2 - 6.8)
10-1/0
20 - 60
45.0
62
Cu
(2.2 - 6.8)
3-3/0
55.0
77
80 (9)
Cu
3-3/0
75.0
99
80 (9)
Cu
6 - 350
120 - 275
90.0
125
kcmil
(14 - 31.1)
Cu
Disconnect
Switch
Torque,
Torque,
Wire
Wire
lb-in
Size *
Size *
(Nm)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
13 - 17
7 - 10.3
18-10
18-14
(1.5 - 1.7)
(8 - 1.2)
17 - 22
18 - 22
14-8
14-10
(1.9 - 2.5)
(2 - 2.5)
17 - 22
18 - 22
14-8
14-10
(1.9 - 2.5)
(2 - 2.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
27 - 40
14-6
18-3
(2.5 - 3.1)
(3.1 - 4.5)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
22 - 27
36 - 53
12-1
10-1/0
(2.5 - 3.1)
(4.1 - 6)
6 - 350
120 - 275
124 - 210
10-1/0
kcmil
(14 - 31.1)
(14 - 23.7)
Installation Instructions
Overload
Max
Range,
Backup
Wire
lb-in
Amps
Fuse,
Size*
(Nm)
Amps
.7 - 1.0
4
14-2
.9 - 1.25
5
14-2
1.1 - 1.6
6
14-2
1.8 - 2.5
10
14-2
2.2 - 3.2
12
14-2
2.8 - 4
16
14-2
4.5 - 6.3
25
14-2
7 - 10
40
14-2
9 - 2
45
14-2
14 - 20
80
14-2
17 - 22
80
14-2
22 - 32
125
14-2
28 - 40
150
14-2
36 - 45
175
14-2
40 - 50
200
14-2
45 - 63
250
14-2
70 - 90
350
14-2/0
80 - 100
400
14-2/0
50 - 200
800
14-2/0
Ground Lug
Torque,
lb-in
(Nm)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
35 (4)
50 (5.6)
50 (5.6)
50 (5.6)
15