BACnet Object Mapping

Table 3 provides a listing of the BACnet objects supported by the configuration preloaded on the XLTR-1000
gateway.
Instance ID
Object Name
AI1
S1 Gas Number
AI2
S1 Concentration
AI3
S1 Alarm State
AI11
S2 Gas Number
AI12
S2 Concentration
AI13
S2 Alarm State
AI21
S3 Gas Number
AI22
S3 Concentration
AI23
S3 Alarm State
AI31
S4 Gas Number
AI32
S4 Concentration
AI33
S4 Alarm State
AI41
S5 Gas Number
AI42
S5 Concentration
AI43
S5 Alarm State
AI51
S6 Gas Number
AI52
S6 Concentration
Page 4 of 8
Table 3: BACnet Object Mapping
Description
Gas Number for Sensor 1
Gas Concentration for
Sensor 1
Alarm State for Sensor 1
Gas Number for Sensor 2
Gas Concentration for
Sensor 2
Alarm State for Sensor 2
Gas Number for Sensor 3
Gas Concentration for
Sensor 3
Alarm State for Sensor 3
Gas Number for Sensor 4
Gas Concentration for
Sensor 4
Alarm State for Sensor 4
Gas Number for Sensor 5
Gas Concentration for
Sensor 5
Alarm State for Sensor 5
Gas Number for Sensor 6
Gas Concentration for
Sensor 6
05.23.2014
0720-168-MC
Units
Multiplier
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
0 - None
No Units
Bit 0 – Caution
1.000000
(95)
Bit 1 – Warning
Bit 2 – Alarm
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
0 - None
No Units
Bit 0 – Caution
1.000000
(95)
Bit 1 – Warning
Bit 2 – Alarm
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
0 - None
No Units
Bit 0 – Caution
1.000000
(95)
Bit 1 – Warning
Bit 2 – Alarm
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
0 - None
No Units
Bit 0 – Caution
1.000000
(95)
Bit 1 – Warning
Bit 2 – Alarm
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
0 - None
No Units
Bit 0 – Caution
1.000000
(95)
Bit 1 – Warning
Bit 2 – Alarm
No Units
0 to 44 (Refer to manual for
1.000000
(95)
definition)
PPM (96)
1.000000 -20 to 1050
1600 Aspen Commons, Suite 210
Middleton, WI, USA
Tel:
(608) 831-1255
Fax: (608) 831-2045
Email: sales@iccdesigns.com