4
Vent Information
A. Venting Termination Minimum Requirements
O
Figure 13.1
All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.
Above Finish Grade (the grade surface
A
12 in.
must be a non-combustible material
12 in.
B
Open door or window: below or to the side
48 in. no OAK
B
12 in.
Open door or window: above
Permanently closed window: above, below
C
6 in.
or to the side
Vertical clearance to a ventilated soffit
18 in.
located above the terminal within a hori-
D
36 in. no OAK
zontal distance of 2 ft from the center-line
of the terminal
E
12 in.
Clearance to unventilated soffit
F
12 in.
Clearance to outside corner
G
12 in.
Clearance to inside corner
Above gas meter/regulator measured from
H
36 in.
horizontal center-line of regulator
36 in. USA
I
Clearance to service regulator vent outlet
72 in. Canada
Clearance to non-mechanical air supply
12 in.
J
inlet to the building or the combustions air
48 in. no OAK
inlet to any other appliance
10 ft horizontal
K
Clearance to mechanical air supply
3 ft vertical
Above paved sidewalk, paved driveway
L
7 ft.
located on public property
Under an open veranda, porch, deck or
M
12 in.
balcony
Electric service: above, below or to the
See Note
N
side (location must not obstruct or interfere
below*
with access)
Adjacent building, fences and protruding
O
24 in.
parts of the structure
Clearance above roof line for vertical
P
12 in.
terminations
*NOTE: Consult local building, fire officials or authorities
having jurisdiction. Local codes or regulations may
require different clearances.
August 3, 2018
D
E
L
C
B
V
FIXED
CLOSED
OPEN
F
V
B
V
Termination Cap
Inside Corner
G
V
A
FIXED
OPEN
V
CLOSED
B
V
A
B
G
Air Supply Inlet
Gas Meter
X
Above grass, top of plants, wood or any other com-
24 in.
bustible
12 in.
Clearance from any forced air intake of other appli-
36 in. no OAK
ance
12 in.
Clearance horizontally from combustible wall
Vented directly through a wall, minimum length of
15 in.
horizontal pipe
6 in. horizontal
Minimum horizontal or vertical terminations must
12 in. vertical
protrude from wall
NOTICE: Do NOT Terminate Vent:
•
In any location that will allow flue gases or soot from
entering or staining the building
•
In any location which could create a nuisance or
hazard
•
In any enclosed or semi-enclosed area such as a
carport, garage, attic, crawl space, under a sun deck or
porch, narrow walkway
•
Closely fenced area, or any location that can build up
a concentration of fumes such as a stairwell, covered
breezeway, etc.
NOTICE: Termination must exhaust above air inlet elevation.
•
It is recommended that at least 60 inches (1.52m) of
vertical pipe be installed when appliance is vented
directly through a wall. This will create a natural draft,
which will help prevent the possibility of smoke or odor
venting into the home during a power outage.
•
It will also keep exhaust from causing a nuisance
or hazard by exposing people or shrubs to high
temperatures.
•
The safest and preferred venting method is to extend
the vent vertically through the roof or above the roof.
7050-145L
SANTA FE FREESTANDING
V
N
N
N
Electrical
V
V
Service
N
V
H
P
G
M
I
X
V
J or K
Restricted Area
13