Table 15. Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Ripple, in DC auxiliary voltage
Operative range
Auxiliary voltage dependence, operate
value
Interrupted auxiliary DC voltage
Interruption
interval
0–50 ms
0–∞ s
Restart time
Table 16. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Harmonic frequency dependence (20% content)
Table 17. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Harmonic frequency dependence (20% content)
Type tests according to standards
ABB
Reference value
Within nominal
range
max. 2%
15% of EL
Full wave rectified
±20% of EL
24-60 V DC ± 20%
100-250 V DC ±20%
Within nominal range
f
r
f
r
2
Within nominal range
f
r
f
r
2
M16706-1 v13
Influence
0.01%/%
0.01%/%
No restart
Correct behaviour at power down
< 300 s
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
±2.5 Hz for 50 Hz
±3.0 Hz for 60 Hz
nd
rd
th
, 3
and 5
harmonic of f
r
1MRK 511 426-BEN B
Influence
±1.0%/Hz
±1.0%
Influence
±1.0%/Hz
±1.0%
IP15778-1 v1