Bay control REC650 2.2
Product version: 2.2
test purposes due to risk of interference
during normal operation.
IEC 61850 quality expander QUALEXP
The quality expander component is used to display the
detailed quality of an IEC/UCA 61850-9-2LE analog channel.
The component expands the channel quality output of a
Merging Unit analog channel received in the IED as per the
IEC 61850-7-3 standard. This component can be used during
the ACT monitoring to get the particular channel quality of the
Merging Unit.
IEC/UCA 61850-9-2LE communication protocol
Optical Ethernet port communication standard IEC/UCA
61850-9-2LE for process bus is supported. IEC/UCA
61850-9-2LE allows Non Conventional Instrument
Transformers (NCIT) with Merging Units (MUs) or stand-alone
MUs to exchange information with the IED, and simplifies SA
engineering. IEC/UCA 61850-9-2LE uses the same port as
IEC 61850-8-1.
LON communication protocol
Existing stations with ABB station bus LON can be extended
with use of the optical LON interface (glass or plastic). This
allows full SA functionality including peer-to-peer messaging
and cooperation between the IEDs.
SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
Monitoring Systems SMS.
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple
substation automation systems including equipment from
different vendors. Disturbance files uploading is provided.
Measurands for IEC 60870-5-103 I103MEAS
103MEAS is a function block that reports all valid measuring
types depending on the connected signals. The set of
connected inputs will control which ASDUs (Application
Service Data Units) are generated.
Measurands user-defined signals for IEC 60870-5-103
I103MEASUSR
I103MEASUSR is a function block with user-defined input
measurands in monitor direction. These function blocks
include the
FunctionType parameter for each block in the
private range, and the
Information number parameter for each
block.
Function status auto-recloser for IEC 60870-5-103 I103AR
I103AR is a function block with defined functions for
autorecloser indications in monitor direction. This block
ABB
GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v4
SEMOD120140-5 v3
SEMOD120134-5 v1
SEMOD120137-5 v4
FunctionType parameter, and the information
includes the
number parameter is defined for each output signal.
Function status earth-fault for IEC 60870-5-103 I103EF
I103EF is a function block with defined functions for earth
fault indications in monitor direction. This block includes the
FunctionType parameter; the information number parameter
is defined for each output signal.
Function status fault protection for IEC 60870-5-103
I103FLTPROT
I103FLTPROT is used for fault indications in monitor
direction. Each input on the function block is specific for a
certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For
example: 68_TRGEN represents the General Trip of the
device and must be connected to the general trip signal
SMPPTRC_TRIP or equivalent.
IED status for IEC 60870-5-103 I103IED
I103IED is a function block with defined IED functions in
monitor direction. This block uses the parameter
FunctionType ; the information number parameter is defined
for each input signal.
Supervison status for IEC 60870-5-103 I103SUPERV
I103SUPERV is a function block with defined functions for
supervision indications in monitor direction. This block
FunctionType parameter; the information number
includes the
parameter is defined for each output signal.
Status for user-defined signals for IEC 60870-5-103
I103USRDEF
I103USRDEF comprises function blocks with user-defined
input signals in monitor direction. These function blocks
FunctionType parameter for each block in the
include the
information number parameter for each
private range, and the
input signal.
Function commands for IEC 60870-5-103 I103CMD
I103CMD is a command function block in control direction
with pre-defined output signals. The signals are in steady
state, not pulsed, and stored in the IED in case of restart.
IED commands for IEC 60870-5-103 I103IEDCMD
I103IEDCMD is a command block in control direction with
defined IED functions. All outputs are pulsed and they are
NOT stored. Pulse-time is a hidden parameter.
Function commands user-defined for IEC 60870-5-103
I103USRCMD
I103USRCMD is a command block in control direction with
user-defined output signals. These function blocks include
FunctionType parameter for each block in the private
the
Information number parameter for each output
range, and the
signal.
1MRK 511 426-BEN B
25