ABB REC650 Product Manual page 32

Relion 650 series
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Bay control REC650 2.2
Product version: 2.2
Table 8. BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
The stated operate time for functions
include the operating time for the binary
inputs and outputs.
Table 9. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
32
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20 ms
3 ms
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
3 ms
1MRK 511 426-BEN B
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
M50609-2 v8
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
-
ABB

Advertisement

Table of Contents
loading

Table of Contents