8.12 CO emissions check

In case air/gas combustion adjustment has been performed
check emissions using reference values in tables 25 and 26.
8.12.1 Access to measuring port
Allow the appliance to stabilize before
performing CO readings.
Let appliance warm up and wait for 2 or 5
minutes for each CO readings.
This will avoid wrong CO readings.
▶ Open a hot water tap and let the appliance work for 2 or 5
minutes.
▶ Remove the screw from the flue adaptor on the left side of
the appliance, as seen in fig. 60.
▶ Insert analyzer probe into the measuring port. The tip of the
probe should be in the center of the flue pipe (approx 1.5"
inserted). Avoid air gaps between probe and measuring
port as they can alter readings.
Fig. 60
Measuring port
Greentherm T9800 SE 160/199 | SEC 199
8.12.2 CO
and CO values
2
CO
max. input
P1
min. input
P2
max. input
P1
min. input
P2
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
values. Changes in these inputs can result in
2
different CO and CO
values on the same appliance.
2
Table 25 CO
& CO target numbers
2
CO
max. input
P1
min. input
P2
max. input
P1
10.0 % - 10.6 %
min. input
P2
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact
CO and CO
values. Changes in these inputs can result in
2
different CO and CO
values on the same appliance.
2
Table 26 CO
& CO target numbers
2
8.12.3 Returning to Service
▶ Remove the analyzer probe and insert the screw into the
flue adaptor.
▶ Touch the symbol
The appliance is ready for normal operation.
Troubleshooting | 59
range (%)
Max. CO level
2
(measured)
Greentherm T9800 SE / SEC
199 000 BTU
Nat. Gas
8.4 % - 9.0 %
< 250 ppm
N/A
< 100 ppm
LP Gas
9.7 % - 10.4 %
< 250 ppm
N/A
< 100 ppm
range (%)
Max. CO level
2
(measured)
Greentherm T9800 SE
160 000 BTU
Nat. Gas
8.5 % - 9.1 %
< 250 ppm
N/A
< 100 ppm
LP Gas
< 250 ppm
N/A
< 100 ppm
to exit service menu.
6 720 816 815 (2018/08)