Installing Communication Transponder Fdcc221S - Siemens FDA241 Technical Manual

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Mounting / Installation
5
Mounting
5.2.4
62
Building Technologies
Fire Safety

Installing communication transponder FDCC221S

Communication transponder FDCC221S may only be installed if the aspirating
smoke detector is connected to FDnet/C-NET. Installation is not permitted in the
case of standalone operation.
Communication transponder FDCC221S has its own ID. The ID of communication
transponder FDCC221S is made visible to the detector line and it replaces the ID
of the aspirating smoke detector.
Installing communication transponder FDCC221S in an aspirating smoke detector
Changes on the type plate when the FDCC221S is installed
1 Mark indicating that the FDCC221S is installed
2 ID adhesive label from FDCC221S for aspirating smoke detector
3 Tear-off adhesive label for installation plan
A6V10334410_h_en_--
2015-09-29