Nibe VVM 310 Installer Manual

Indoor module
Hide thumbs Also See for VVM 310:

Advertisement

Quick Links

Installer manual
NIBE™ VVM 310
Indoor module
IHB GB 1338-3
231175

Advertisement

Table of Contents
loading

Summary of Contents for Nibe VVM 310

  • Page 1 Installer manual NIBE™ VVM 310 Indoor module IHB GB 1338-3 231175...
  • Page 2 A detailed explanation of the button functions can be found on page 33. How to scroll through menus and make different settings is described on page 35. The mode for setting the indoor temperature is reached, when in the start mode in the main menu, by pressing the OK button twice.
  • Page 3: Table Of Contents

    Connecting accessories Dimensions and setting-out coordinates 6 Commissioning and adjusting Hot water capacity Preparations Technical specifications Filling and venting Electrical circuit diagram, 3 x 400V Connecting the circulation pumps Item register Start-up and inspection NIBE™ VVM 310 Table of Contents |...
  • Page 4: Important Information

    This symbol indicates tips on how to facilitate using the product. Marking VVM 310 is CE marked and fulfils IP21. The CE marking means that NIBE ensures that the product meets all regulations that are placed on it based on relevant EU directives. The CE mark is obligat- ory for most products sold in the EU, regardless where they are made.
  • Page 5 Safety valve Electricity (page 19) Connected communication Circuit fuses Fuses, indoor module Fuses property Outside sensor Room sensor Current sensor Safety breaker Earth circuit-breaker Setting of emergency mode thermostat Miscellaneous Docked to NIBE™ VVM 310 Chapter 1 | Important information...
  • Page 6 Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: info@nibe.fi www.nibe.fi AIT France, 10 rue des Moines, 67000 Haguenau Tel : 03 88 06 24 10 Fax : 03 88 06 90 15 E-mail: info@nibe.fr www.nibe.fr NIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QG Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: info@nibe.co.uk www.nibe.co.uk...
  • Page 7: Delivery And Handling

    Leave a space of 500 mm in front of the product. All VVM 310 should be transported and stored vertically service on VVM 310 can be carried out from the front. in a dry place. The VVM 310 may, however, be carefully laid on its back when being moved into a building.
  • Page 8: Supplied Components

    Supplied components Outside sensor Room sensor Current sensor Location The kit of supplied items is placed on top of the product. Chapter 2 | Delivery and handling NIBE™ VVM 310...
  • Page 9: Removing The Covers

    1. Remove the screws from the upper and lower edges. 2. Twist the cover slightly outward. 3. Move the cover backwards and slightly to the side. 4. Pull the cover to one side. 5. Pull the cover forwards. NIBE™ VVM 310 Chapter 2 | Delivery and handling...
  • Page 10: Indoor Module's Design

    AA4-XJ3 VVM 310 AA4-XJ3 AA3-X4 BF1* BT30 AA1-X3 AA1-SF1 BT54 AA1-X7 AA1-X1 QN35 GP12 XL30 XL18 XL19 *Applies to Germany, Switzerland and Austria Available as accessory EMK 310 in other markets. Chapter 3 | Indoor module's design NIBE™ VVM 310...
  • Page 11 Pipe connections Auxiliary relay, emergency mode. Switch Connection, heating medium flow line G20 int. W130 Network cable for NIBE Uplink Connection, heating medium return line G20 int. Connection, cold water G20 int. Connection, hot water G20 int. Miscellaneous Connection, docking in heating medium G20 int.
  • Page 12: Pipe Connections

    Switch (SF1) must not be moved to " " or " " VVM 310 covers most of the heating and hot water until VVM 310 has been filled with water. requirement down to the heat pump stop temperature.
  • Page 13 Meaning Shut-off valve Tapping valve Non-return valve Shunt / shuttle valve Safety valve Thermometer Trim valve Temperature sensor Expansion vessel Pressure gauge Circulation pump Particle filter Flow meter EMK 310 Heat exchanger NIBE™ VVM 310 Chapter 4 | Pipe connections...
  • Page 14: Dimensions And Pipe Connections

    Connection, docking in heating medium G20 int. Connection, docking out heating medium G20 int. XL18 Connection, docking in high temp Ø22 mm XL19 Connection, docking out high temp Ø22 mm XL30 Connection, expansion vessel G20 int. Chapter 4 | Pipe connections NIBE™ VVM 310...
  • Page 15: Installation Alternative

    F2040 all versions F2300 VVM 310 can be connected to extra water heater, see below. Further option information is available at www.nibe.eu and in the respective assembly instructions for the ac- cessories used. See page 60 for a list of the accessories that can be used with VVM 310.
  • Page 16 Unit box BT53 Temperature sensor, solar panel Expansion vessel Solar panel GP30 Pump station SPS 10, SPS20 GP30 Pump station SPS 10, SPS 20 Safety valve, solar Pump, solar QM43 Shut-off valve Chapter 4 | Pipe connections NIBE™ VVM 310...
  • Page 17 60 °C. If the factory setting is changed, national regulations VVM 310 is not equipped with shut off valves; these must be observed. The setting is made in menu 5.1.1 must be installed outside the indoor module to facilit- (See page 51).
  • Page 18 -QM40 -GP15 -XL19 -HQ1 -QM41 -EB15 -QM1 *EMK 310 is included in VVM 310 for Germany, Switzerland and Austria. Available as accessory in other markets. Connecting EMK 300 Installing energy measurement kit EMK 300 (BF2) to VVM 310. -FL2 -CM1...
  • Page 19 Adjust the hot water system so that the temperature does not fall below 50 °C at the ends of the system. -FL1 -RM1 -QM40 -GP9 -FL2 -CM1 -EB15 NIBE™ VVM 310 Chapter 4 | Pipe connections...
  • Page 20 The POOL 310 accessory is required for this connection. -CL11 -EP5 -BT51 -GP9 -HQ4 -AA25 -CL11 -GP12 -FL2 -CM1 -CL11-QN19 -EB15 -EB101 -FL10 -EB101 -RN10 -QM40 -HQ1 -QM41 -QM1 Chapter 4 | Pipe connections NIBE™ VVM 310...
  • Page 21: Electrical Connections

    5 Electrical connections General Caution When VVM 310 must be run with an older All electrical equipment, except the outdoor sensors, outdoor section, the program version in the room sensors and the current sensors are ready connec- outdoor section must be V51 or later.
  • Page 22 1. Insert the screwdriver (A) and pry the catch care- fully downwards (B). 1. Push the catch down. 2. Angle out the cover and remove it. 2. Angle out the cover and remove it. Chapter 5 | Electrical connections NIBE™ VVM 310...
  • Page 23 Cable lock Use a suitable tool to release/lock cables in the indoor module terminal blocks. NIBE™ VVM 310 Chapter 5 | Electrical connections...
  • Page 24: Connections

    Power connection Install the sensor in a neutral position where the set VVM 310 must be installed via an isolator switch with temperature is required. A suitable location is on a free a minimum breaking gap of 3 mm. Minimum cable inner wall in a hall approx.
  • Page 25 Communication If VVM 310 is to be connected to the heat pump, it is connected to terminals X4:13, X4:14 and X4:15 on the input card (AA3). F20XX VVM500 VVM 310 AA3-X4 F2026 VVM500 NIBE™ VVM 310 Chapter 5 | Electrical connections...
  • Page 26: Settings

    The supply temperature is set in emergency mode using overload, the power is reconnected to another/other a thermostat (FD1-BT30). It can be set to 35 (pre-set, phases. for example underfloor heating) or 45 °C (for example radiators). Chapter 5 | Electrical connections NIBE™ VVM 310...
  • Page 27 Output locking VVM 310 follows applicable building regulations (BBR). This means that the maximum power output (maxim- um installed electrical output for heating) can be locked in menu 5.1.13. To then change the maximum power output, parts of the product must be replaced.
  • Page 28: Optional Connections

    Caution If an external switch function or sensor is con- Load monitor nected to VVM 310, the function to use input or output must be selected in menu 5.4, see When many power consumers are connected in the page 53.
  • Page 29 (A = SG Ready A and B = SG Ready B ): below. Blocking (A: Closed, B: Open) "SG Ready" is active. The compressor in the heat pump and additional heat is blocked like the day's tariff blocking. NIBE™ VVM 310 Chapter 5 | Electrical connections...
  • Page 30: Connecting Accessories

    VVM 310. VVM 500 F1X45 Externt AA3-X7 Caution The relay outputs can have a max load of 2 A (230 V AC) in total. Chapter 5 | Electrical connections NIBE™ VVM 310...
  • Page 31: Commissioning And Adjusting

    (QM20). Venting the climate system 1. Turn off the power supply to VVM 310. 2. Vent VVM 310 through the vent valve (QM20) and the other climate systems through their relevant vent valves.
  • Page 32: Connecting The Circulation Pumps

    Connecting the circulation pumps After the system has been filled with water and vented, connect the circulation pumps' switches. VVM 310 Chapter 6 | Commissioning and adjusting NIBE™ VVM 310...
  • Page 33: Start-Up And Inspection

    During the start up guide the reversing valves and the you can scroll between using the control knob. shunt valve are run backward and forwards to help vent VVM 310. Caution As long as the start guide is active, no function in the heat pump will start automatically.
  • Page 34: Nibe™ Vvm

    Commissioning without heat pump Pump speed The indoor module can be run without heat pump, as Both the circulation pumps in VVM 310 are frequency only an electric boiler, to produce heat and hot water, controlled and set themselves using control and extern- for example before the heat pump is installed.
  • Page 35: Control - Introduction

    The control knob can be turned to the right or left. You can: scroll in menus and between options. increase and decrease the values. change page in multiple page instructions (for example help text and service info). NIBE™ VVM 310 Chapter 7 | Control - Introduction...
  • Page 36: Menu System

    These two symbols indicate whether the compressor in the outdoor unit or addi- tional heat is blocked in VVM 310. These can, for example, be blocked de- pending on which operating mode is se- lected in menu 4.2, if blocking is sched- uled in menu 4.9.5 or if an alarm has oc-...
  • Page 37 To select another option: 1. Mark the applicable option. One of the options is pre-selected (white). 2. Press the OK button to confirm the selected option. The selected option has a green tick. NIBE™ VVM 310 Chapter 7 | Control - Introduction...
  • Page 38 1. Turn the control knob until one of the arrows in the top left corner (at the page number) has been marked. 2. Press the OK button to skip between the steps in the start guide. Chapter 7 | Control - Introduction NIBE™ VVM 310...
  • Page 39: Control - Menus

    Menu 1.3 - scheduling Default value: 0 In the menu scheduling indoor climate (heating) is scheduled for each weekday. You can also schedule a longer period during a selected period (vacation) in menu 4.7. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 40 You can select heating curve and read off how the changing the desired days. flow line temperature changes at different outdoor temperatures here. Chapter 8 | Control - Menus NIBE™ VVM 310...
  • Page 41 2. Press the OK button. 3. Follow the grey line up to the heat curve and out to the left to read off the value for the supply temperature at the selected outdoor temperature. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 42 Default value: 0 °C Set the minimum temperature on the supply temper- ature to the climate system. This means that VVM 310 Select a change in the heating curve at a certain out- never calculates a temperature lower than that set door temperature here.
  • Page 43 "outdoor temp. point" is set to "-2" and "change in curve" is increased until the desired room temperature is maintained. Caution Wait 24 hours before making a new setting, so that the room temperature has time to stabilise. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 44: Menu 2 - Hot Water

    Schedule: The schedule to be changed is selected here. to the right. Activated: Scheduling for the selected period is activ- When the time has run out VVM 310 returns to the ated here. Set times are not affected at deactivation. mode set in menu 2.2.
  • Page 45 "operating time" decide how long the hot water circu- lation pump must run per operating instance. "downtime" decide how long the hot water circulation pump must be stationary between operating instances. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 46: Menu 3 - Info

    Menu 3.3 - add. heat info Information about the additional heat settings, operat- ing status and statistics can be obtained here. No changes can be made. Chapter 8 | Control - Menus NIBE™ VVM 310...
  • Page 47: Menu 4 - My System

    Settings of indoor module work mode. Menu 4.1.3 - internet Menu 4.1 - plus functions Here you make settings for connecting VVM 310 to the Settings for any additional functions installed in VVM internet. 310 can be made in the sub menus.
  • Page 48 Menu 4.1.3.9 - proxy settings the internet. You can set proxy settings for your installation here. A connected user has a user account in NIBE Uplink™ Proxy settings are used to give connection information which have been given permission to control and/or to a intermediate server (proxy server) between the monitor your installation.
  • Page 49 You can select what icon should be visible when the Setting range: compressor, addition, heating, cooling door to VVM 310 is closed. You can select up to 3 icons. If you select more, the ones you selected first will disap- The indoor module operating mode is usually set to pear.
  • Page 50 Default value: 700 diff. between additional steps Setting range: 0 – 1000 Default value: 100 Degree minutes are a measurement of the current heating requirement in the house and determine when Chapter 8 | Control - Menus NIBE™ VVM 310...
  • Page 51 Blocking: The desired blocking is selected here. Conflict: If two settings conflict with each other a red exclamation mark is displayed. Blocking the compressor in the outdoor unit. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 52: Menu 5 - Service

    Setting software controlled in and outputs on the input circuit board (AA3). factory setting service Total reset of all settings (includ- ing settings available to the user ) to default values. Chapter 8 | Control - Menus NIBE™ VVM 310...
  • Page 53 If the installation has more than one cli- auto: The heating medium pump runs according to mate system, individual maximum flow temperatures the current operating mode for VVM 310. can be set for each system. continuous: Continuous operation.
  • Page 54 Here you set the max. electrical output of the internal There are two ways of activating connected accessories. electrical addition in VVM 310 and the fuse size for the You can either mark the alternative in the list or use installation.
  • Page 55 Menu 5.6 - forced control You can force control the different components in the indoor module and any connected accessories here. NIBE™ VVM 310 Chapter 8 | Control - Menus...
  • Page 56 Set the speed at which the charge pump is to operate in the present operating mode. auto: The charge pump selects optimal speed for the current operating mode for VVM 310. manual: The speed of the charge pump is adjustable between 0 and 100%.
  • Page 57: Service

    (°C) (kOhm) Servicing should only be carried out by persons 351.0 3.256 with the necessary expertise. 251.6 3.240 When replacing components on VVM 310 only 182.5 3.218 replacement parts from NIBE may be used. 133.8 3.189 99.22 3.150 Emergency mode 74.32...
  • Page 58 VVM 310 is equipped with a USB socket in the display the one selected, the correct file can be selected by unit. This USB socket can be used to connect a USB "choose another file". memory to update the software, save logged informa- start updating tion and handle the settings in VVM 310.
  • Page 59 Set whether the present measurement values from VVM 310 are to be saved in a log on the USB memory. Log for longer periods 1. Set the desired interval between loggings. 2. Tick “activated". 3. The present values from VVM 310 are saved in a file in the USB memory at the set interval until “activated"...
  • Page 60: Disturbances In Comfort

    If the room temperature is only high in cold weather the curve slope in menu 1.9.1 (heating curve) needs to be adjusted down. Chapter 10 | Disturbances in comfort NIBE™ VVM 310...
  • Page 61 Wait until the temperature condition has been re- set. Minimum time between compressor starts has not been reached. Wait 30 minutes and check if the compressor has started. Alarm tripped. Follow the display instructions. NIBE™ VVM 310 Chapter 10 | Disturbances in comfort...
  • Page 62: Accessories

    Part no. 067 064 Control unit for external heat source SCA 35 DEH 310 (oil/electricity/gas) SCA 35 means that VVM 310 can be connected to solar Part no. 067 249 heating. Energy measurement kit EMK 310* Part no. 067 245 Part no.
  • Page 63: Technical Data

    12 Technical data Dimensions and setting-out coordinates NIBE™ VVM 310 Chapter 12 | Technical data...
  • Page 64: Hot Water Capacity

    Hot water capacity Varmvattenkapacitet VVM310 Tappflöde (l/m) Ekonomi Normal Ekonom Normal Volym varmvatten (liter) Chapter 12 | Technical data NIBE™ VVM 310...
  • Page 65: Technical Specifications

    IP 21 3x400V 3x400V Maxim heat pump output NIBE F2025 with program version 51 or later Maxim heat pump output NIBE F2026 with program version 51 or later Maximum heat pump output NIBE F2300 Maximum heat pump output NIBE F2040...
  • Page 66 Height (with base) 1830 – 1850 Required ceiling height 1910 Weight (excl. packaging and without water) Part number, EMK 310 included (only for Germany, Switzerland and Austria) 069 084 Part no. 069 430 Chapter 12 | Technical data NIBE™ VVM 310...
  • Page 67: Electrical Circuit Diagram, 3 X 400V

    Electrical circuit diagram, 3 x 400V NIBE™ VVM 310 Chapter 12 | Technical data...
  • Page 68 Chapter 12 | Technical data NIBE™ VVM 310...
  • Page 69 NIBE™ VVM 310 Chapter 12 | Technical data...
  • Page 70 Chapter 12 | Technical data NIBE™ VVM 310...
  • Page 71 NIBE™ VVM 310 Chapter 12 | Technical data...
  • Page 72: Item Register

    Connection of external heat source, 16 Status lamp, 33 Extra hot water heaters, 13 Switch, 33 Two or more climate systems, 16 Disturbances in comfort, 58 Water heater with immersion heater, 13 Alarm, 58 Chapter 13 | Item register NIBE™ VVM 310...
  • Page 73 Standby mode, 55 Temperature sensor data, 55 USB service outlet, 55 Setting a value, 35 Settings, 24 Emergency mode, 24 Standby mode, 24, 55 Power in emergency mode, 24 Start guide, 31 NIBE™ VVM 310 Chapter 13 | Item register...
  • Page 74 Chapter 13 | NIBE™ VVM 310...
  • Page 76 NIBE AB Sweden Hannabadsvägen 5 Box 14 SE-285 21 Markaryd info@nibe.se www.nibe.eu 231175...