Definitions; Safur Resistor Data; Terminals And Cable Lead-Through Data Of Factory-Installed Chopper/Resistor Cubicles - ABB ACS880-07CLC Hardware Manual

Hide thumbs Also See for ACS880-07CLC:
Table of Contents

Advertisement

ACS880-
Module
Resistor type
607LC-...
type
2400-7
6 ×
NBRW-
SAFUR200F500)
669C

Definitions

U
Nominal voltage
N
R
Nominal (recommended) resistance of the resistor assembly of one chopper module
n
Resistance of specified resistors (per chopper module). This is also the minimum allowed resistance
R
min
for the resistor assembly.
Maximum short-term (1 min in every 10 min) braking power
P
brmax
P
Maximum continuous power rating
brcont
I
Maximum peak current
max
P
Maximum braking power for the specified duty cycle
br
I
Rms current for the specified duty cycle
rms

SAFUR resistor data

The following SAFUR resistors are available separately.
Type
SAFUR125F500
SAFUR210F575
SAFUR200F500
SAFUR180F460
U
Nominal voltage
N
R
Resistance
E
Short energy pulse that the resistor assembly will withstand each 400 seconds
R
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
Rcont
400 seconds.
IPxx
Degree of protection
Terminals and cable lead-through data of factory-installed
chopper/resistor cubicles
See the dimension drawings delivered with the unit.
P
R
brmax
min
kW
ohm
6 × (2 ×
2422
1.35
U
R
N
V
ohm
500
4.0
575
3.4
500
2.7
460
2.4
Duty cycle
(1/5 min)
I
I
P
max
rms
brcont
P
br
A
A
kW
kW
5010
582
324
1000
E
R
kJ
3600
4200
5400
6000
Resistor braking 205
Duty cycle
(10/60 s)
I
P
I
rms
br
rms
A
kW
A
894
1724
1542
64800
P
Rcont
IPxx
kW
9.0
IP00
10.5
IP00
13.5
IP00
15.0
IP00
dissipates in
R
E
R
kJ