Ac Output Cable Connection Procedure - ABB PVS800-57B Maintenance Manual

Central inverters
Hide thumbs Also See for PVS800-57B:
Table of Contents

Advertisement

44 Electrical installation

AC output cable connection procedure

Refer to the dimension drawings in the PVS800-57B central inverters hardware manual
(3AXD50000048300 [EN]).
1. Remove the shroud from the output power terminals.
2. Put the cable(s) into the cabinet.
3. If it is a shielded cable, prepare the cable ends and do the 360° grounding at the
cabinet entry. Connect the twisted shield of the AC output cable(s) to the cabinet PE
(ground) busbar with a cable lug.
4. Connect the phase conductors to terminals L1, L2 and L3.
5. If it is present, connect the separate PE/grounding conductor to the cabinet PE
(ground) busbar.
6. Install the shroud on to the output power terminals.
AC output terminals L1, L2, L3
a) Cable lead-throughs
L1
L2
L3
a

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents