Platinum Tools Fault Trapper TFT100 User Manual page 11

Transient fault location for energized dedicated circuit breakers
Hide thumbs Also See for Fault Trapper TFT100:

Advertisement

Note! Use only on Energized Dedicated Circuits, Max 40 Amps.
Connecting the Fault Trapper 40A In-Line Adapter
Module to Circuit Breakers (USA)
To connect to a 120VAC Standard Breaker (up to 40 Amps)
All connections to the Fault Trapper 40A In-Line Adapter Module are
made using plug-in terminal block connectors; torque screws to 7in-
lbs:
1. Noting the alignment of the Terminal Block Connector relative
to the Load Terminal Jack on the 40A In-Line Adapter Module,
remove the hot wire from the breaker being tested and insert it
into the Terminal Block Connector so that it is matched with Load
Terminal "L1". Torque down the fastening screw to 7 in-lbs.
2. Strip the ends off a white jumper wire and connect one end
to the neutral/ground bus bar and insert the other end into
the Load Terminal Block Connector so that it is matched with
Terminal "L2". Torque down the fastening screw to 7 in-lbs.
Caution - Turn off power to the circuit the In-
Line Adapter is being connected to!
120VAC Connection Diagram
Page 11 of 24