Table 38. Frequency protection (FRPFRQ) main settings
Parameter
Values
(Range)
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/
dt
7=Freq> OR df/
dt
Start value Freq>
0.900...1.200
Start value Freq<
0.800...1.100
Start value df/dt
-0.200...0.200
Operate Tm Freq
80...200000
Operate Tm df/dt
120...200000
Unit
Step
Default
1=Freq<
xFn
0.001
1.050
xFn
0.001
0.950
xFn /s
0.005
0.010
ms
10
200
ms
10
400
1MRS756890 D
Issued: 2010-06-29
Description
Frequency
protection
operation mode
selection
Frequency start
value
overfrequency
Frequency start
value
underfrequency
Frequency start
value rate of
change
Operate delay
time for
frequency
Operate delay
time for
frequency rate
of change