Product version: 3.0
Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Start Value
Time multiplier
Operate delay time
Operating curve
2)
type
1) Not included in REM615
2) For further reference please refer to the Operating characteristics table
Function
PHLPTOC
1)
PHHPTOC
PHIPTOC
PHLPTOC
1)
PHHPTOC
PHLPTOC
1)
PHHPTOC
PHIPTOC
PHLPTOC
1)
PHHPTOC
PHIPTOC
Value (Range)
Step
0.05...5.00 x I
0.01
n
0.10...40.00 x I
0.01
n
1.00...40.00 x I
0.01
n
0.05...15.00
0.05
0.05...15.00
0.05
40...200000 ms
10
40...200000 ms
10
20...200000 ms
10
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
1MRS756890 D
Issued: 2010-06-29
31