Table 22. Insulation tests
Description
Dielectric tests
• Test voltage
Impulse voltage test
• Test voltage
Insulation resistance
measurements
• Isolation resistance
Protective bonding
resistance
• Resistance
Table 23. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
Table 24. Product safety
Description
LV directive
Standard
28
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
>100 MΏ, 500 V DC
<0.1 Ώ, 4 A, 60 s
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Reference
2006/95/EC
EN 60255-27 (2005)
EN 60255-1 (2009)
1MRS756890 D
Issued: 2010-06-29
Reference
IEC 60255-5 and
IEC 60255-27
IEC 60255-5 and
IEC 60255-27
IEC 60255-5 and
IEC 60255-27
IEC 60255-27
Requirement
Class 2
Class 2
Class 2
ABB