Motor Protection and Control
REM615
Product version: 3.0
Protection functions
Table 27. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Operation accuracy
2)3)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
1) Not included in REM615
2) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on
stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one phase with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
3) Includes the delay of the signal output contact
4) Includes the delay of the heavy-duty output contact
30
PHLPTOC
1)
PHHPTOC
and
PHIPTOC
PHIPTOC:
I
= 2 x set Start
Fault
value
I
= 10 x set Start
Fault
value
1)
PHHPTOC
and
PHLPTOC:
I
= 2 x set Start
Fault
value
Value
Depending on the frequency of the current
measured: f
±2 Hz
n
±1.5% of the set value or ±0.002 x I
±1.5% of set value or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0% of the set value
(at currents in the range of 10...40 x I
Minimum
Typical
16 ms
19 ms
11 ms
12 ms
22 ms
24 ms
< 40 ms
Typical 0.96
< 30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n x f
n
...
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1MRS756890 D
Issued: 2010-06-29
n
n
)
n
)
n
Maximum
23 ms
14 ms
25 ms
4)
, where n = 2, 3, 4, 5,
ABB