ABB Relion REM615 Product Manual page 26

Relion 615 series motor protection and control
Hide thumbs Also See for Relion REM615:
Table of Contents

Advertisement

Motor Protection and Control
REM615
Product version: 3.0
Table 21. Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst
disturbance test:
• Common mode
• Differential mode
Electrostatic discharge test:
• Contact discharge
• Air discharge
Radio frequency interference
tests:
Fast transient disturbance
tests:
• All ports
Surge immunity test:
• Communication
• Other ports
Power frequency (50 Hz)
magnetic field:
• Continuous
• 1-3 s
26
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f=150 kHz-80 MHz
10 V/m (rms)
f=80-2700 MHz
10 V/m
f=900 MHz
20 V/m (rms)
f=80-1000 MHz
4kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1000 A/m
1MRS756890 D
Issued: 2010-06-29
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
IEC 60255-22-6, class III
IEC 61000-4-6
IEC 61000-4-3
IEC 60255-22-3, class III
ENV 50204
IEC 60255-22-3, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
ABB